Relay
output
1
function
(2.3.4.2)
Setting value
Signal content
0 = Not used
Out of operation
1 = Ready
The frequency converter is ready to operate
2 = Run
The frequency converter operates (motor is running)
3 = Fault
A fault trip has occurred
4 = Fault inverted
A fault trip has not occurred
5 = FC overheat warning
The heat-sink temperature e70 C
6 = External fault or warning
Fault or warning depending on par.
7 = Reference fault or warning
Fault or warning depending on par.
- if analogue reference is 4—20 mA and signal is <4mA
8 = Warning
Always if warning exists
9 = Reversed
The reverse command has been selected
10 = Preset speed 1
The preset speed has been selected with digital input
11 = At speed
The output frequency has reached the set reference
12 = Motor regulator activated
Overvoltage or overcurrent regulator was activated
13 = Output frequency limit supervision
The output frequency goes outside the set super-
vision low limit/high limit (see parameter ID's
below)
14 = Control from I/O terminals
I/O control mode selected (in menu M3)
15 = Thermistor fault or warning (Appl.2)
The thermistor input of option board indicates over-
temperature. Fault or warning depending on par.
.
16 = Actual value supervision
Actual value supervision is active
17 = Cooling OK
Table 30. Output signals via relay outputs RO1 and RO2.
315
Output frequency limit supervision function
(2.5.4)
0 No supervision
1 Low limit supervision
2 High limit supervision
If the output frequency goes under/over the set limit (ID316) this function generates a warning
message via the relay output RO1 or RO2 depending on the settings of parameters ID313 and
ID1513.
316
Output
frequency
limit
supervision
value
(2.5.5)
Selects the frequency value supervised by parameter ID315. See Figure 8.