Automatic restart: Start function
(2.8.3)
The Start function for Automatic restart is selected with this parameter. The parameter defines
the start mode:
0 = Start with ramp
1 = Flying start
2 = Start according to
727
Response
to
undervoltage
fault
(2.7.4)
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to
3 = Fault, stop mode after fault always by coasting
For the undervoltage limits, see the product's user's manual.
730
Input phase supervision
(2.7.3)
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to
3 = Fault, stop mode after fault always by coasting
The input phase supervision ensures that the input phases of the frequency converter have an
approximately equal current.
731
Automatic
restart
(2.1.16)
The Automatic restart is taken into use with this parameter.
0 = Disabled
1 = Enabled
The function resets the following faults (max. three times) (see the product's user's manual:
Overcurrent (F1)
Overvoltage (F2)
Undervoltage (F9)
Frequency converter overtemperature (F14)
Motor overtemperature (F16)
Reference fault (F50)
732
Response to thermistor fault
(2.7.20)
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to
3 = Fault, stop mode after fault always by coasting
Setting the parameter to 0 will deactivate the protection.