32 • vacon
Description of parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
%
100%
63%
ID378
t [s]
NX12K74
Filtered
signal
Unfiltered
signal
340
PID
error
value
inversion
(2.9.9)
This parameter allows you to invert the error value of the PID controller (and thus the
operation of the PID controller).
0 No inversion
1 Inverted
378
AI1
signal
filter
time
(2.2.8)
When this parameter is given a value greater than
0 the function that filters out disturbances from the
incoming analogue signal is activated.
Long filtering time makes the regulation response
slower. See Figure 10.
Figure 10. AI1 signal filtering
379
AI1
signal range
(2.2.3)
0 Signal range 0...20 mA
1 Signal range 4...20 mA
2 Signal range 0...10 V
3 Signal range 2...10 V
380
AI1 custom setting minimum
(2.2.5)
381
AI1 custom setting maximum
(2.2.6)
These parameters set the analogue input signal for any input signal span between
0.00...100.00%. However, the max value of par. ID380 cannot be greater than the value set for
parameter ID381, and the min value of par. ID381 cannot be smaller than the max value of par.
ID380.
Note: Parameter ID379
AI1 signal range
is inactivated if ID380 0% or ID381 100%. See also