48 • vacon
Description of parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
852 to
859
Fieldbus
data
out
selections
1
to
8
6
(2.11.1
to
2.11.8)
Using these parameters, you can monitor any monitoring or parameter value from the fieldbus.
Enter the ID number of the item you wish to monitor for the value of these parameters.
Some typical values:
1
Output frequency
15
Digital inputs 1,2,3 statuses
2
Motor speed
16
Digital inputs 4,5,6 statuses
3
Motor current
17
Digital and relay output statuses
4
Motor torque
25
Frequency reference
5
Motor power
26
Analogue output current
6
Motor voltage
27
AI3
7
DC link voltage
28
AI4
8
Unit temperature
31
AO1 (expander board)
9
Motor temperature
32
AO2 (expander board)
13
AI1
37
Active fault 1
14
AI2
45
Motor current (drive independent)
given with one decimal point
Table 4-32.