12 • vacon
Parameter lists
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
3.4.3
Analogue output 3
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.3.3.1
0 13
4
1535
0=Not used
1=Output freq. (0—f
max
)
2=Freq. reference (0—f
max
)
3=Motor speed (0—Motor
nominal speed)
4=Motor current (0—I
nMotor
)
5=Motor torque (0—T
nMotor
)
6=Motor power (0—P
nMotor
)
7=Motor voltage (0-U
nMotor
)
8=DC-link volt (0—1000V)
9=PID controller ref. value
10=PI contr. act. temp
11=PI contr. temperature
error value
12=PID controller output
13=Pressure from PT11,
pump inlet
P2.3.3.2
0,00 10,00 s 1,00
1536 0=No filtering
P2.3.3.3
0
1
0
1537 0=Not inverted
1=Inverted
P2.3.3.4
0
1
0
1538 0=0 mA
1=4 mA
P2.3.3.5
10 1000 % 100
1539
Table 14. Analogue output 3 signals
3.4.4
Relay output 1
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.3.4.1
B.1
1549
P2.3.4.2
0 18
2
313
0=Not used
1=Ready
2=Run
3=Fault
4=Fault inverted
5=FC overheat warning
6=Ext. fault or warning
7=Ref. fault or warning
8=Warning
9=Reversed
10=Preset speed 1
11=At speed
12=Mot. regulator active
13=OP freq. limit superv.1
14=Control place: IO
15=Thermistor fault/warn.
16=Actual value supervision
17=Cooling OK
18=Alarm latched
P2.3.4.3
0
1
0
1540
0=Not inverted
1=Inverted
Table 15. Relay output 1 signals