8.1
Cable installation and the UL standards
C must be used. The cable must be suitable for use on a circuit
capable of delivering not more than 100,000 rms symmetrical amperes, 600V maximum. Use Class
1 wire only.
The tightening torques of the terminals are given in Table 19.
* Tightening torque of terminal connection to the isolative base in Nm/in-lbs. NOTE: This value is needed only
if the motor connection is made directly to the converter (no devices between converter and motor).
** Apply counter torque to the nut on the other side of the terminal when tightening/loosening the terminal
screw in order to avoid damage to the terminal.
Table 19. Tightening torques of terminals
Type
Frame
Tightening torque
[Nm]
NX_2 0261—0300
NX_5 0261—0300
NX_6 0125—0208
FR9
40/22*
NX_5 0385—1450
FR10-14
40**
NX_6 0261—1180
FR10-14
40**