CABLING AND CONNECTIONS
vacon • 47
24-hour s358 (0)201 212 575 • Email: [email protected]
6
6.2.6.3
Low-harmonic drives
Table 15. Cable and aR fuse sizes for Vacon NX_5 low-harmonic drive
Frame
Type
I
L
[A]
Bussmann/Ferraz
Shawmut fuse type
Fuse I
n
[A]
Mains and motor
cable
1)
[mm
2
]
No. of
supply
cables
No. of
motor
cables
AF9
NXC0261 5
261
No additional drive fuses needed
Cu: 3*185+95 or
2*(3*120+70)
Even/Odd
Even/Odd
NXC0300 5
300
No additional drive fuses needed
Cu: 2*(3*120+70)
Even/Odd
Even/Odd
AF10
NXC0385 5
385
No additional drive fuses needed
Cu: 2*(3*120+70)
Al: 2*(3*185Al+57Cu)
Even/Odd
Even/Odd
NXC0460 5
460
No additional drive fuses needed
Cu: 2*(3*150+70)
Al: 2*(3*240Al+72Cu)
Even/Odd
Even/Odd
NXC0520 5
520
No additional drive fuses needed
Cu: 2*(3*185+95)
Al: 2*(3*300Al+88Cu)
Even/Odd
Even/Odd
AF12
NXC0650 5
650
No additional drive fuses needed
Cu: 4*(3*95+50)
Al: 4*(3*150Al+41Cu)
Even/Odd
Even
NXC0730 5
730
No additional drive fuses needed
Cu: 4*(3*120+70)
Al: 4*(3*185Al+57Cu)
Even/Odd
Even
NXC0820 5
820
No additional drive fuses needed
Cu: 4*(3*150+70)
Al: 4*(3*185Al+57Cu)
Even/Odd
Even
NXC0920 5
920
No additional drive fuses needed
Cu: 4*(3*150+70)
Al: 4*(3*240Al+72Cu)
Even/Odd
Even
NXC1030 5
1030
No additional drive fuses needed
Cu: 4*(3*185+95)
Al: 4*(3*300Al+88Cu)
Even/Odd
Even
AF13
NXC1150 5
1150
No additional drive fuses needed
Cu:5*(3*150+70)
Al:6*(3*185+57Cu)
Even/Odd
Even/Odd
NXC1300 5
1300
No additional drive fuses needed
Cu:5*(3*185+95)
Al:6*(3*240+72Cu)
Even/Odd
Even/Odd
NXC1450 5
1450
No additional drive fuses needed
Cu:6*(3*185+95)
Al:6*(3*240+72Cu)
Even/Odd
Even/Odd
AF14
NXC1770 5
1770
No additional drive fuses needed
Cu: 6*(3*240+120)
Al: 8*(3*240+72Cu)
Even
Even
NXC2150 5
2150
No additional drive fuses needed
Cu: 8*(3*185+95)
Al: 8*(3*300+88Cu)
Even
Even
NXC2700 5
2700
No additional drive fuses needed
Cu: 8*(3*185+95)
Al: 8*(3*300+88Cu)
Even
Even
1)
Based on correction factor 0.7. Cables are laid on a cable ladder side by side, three ladders on top of each
other. Ambient temperature is 30°C (86°F). EN60204-1 and IEC 60364-5-523.