MOUNTING
vacon • 29
24-hour s358 (0)201 212 575 • Email: [email protected]
5
5.6
Cooling
5.6.1
Free space around the cabinet
Enough space must be left above and in front of the cabinet to ensure sufficient cooling and space
for maintenance.
The amount of cooling air required is indicated in the table below. Also make sure that the
temperature of the cooling air does not exceed the maximum ambient temperature of the
converter.
Figure 8.Space to be left free above (left) and in front of (right) the cabinet
Table 10. Required cooling air for NXC 6- and 12-pulse drives
Type
Cooling air required [m
3
/h)
0261—0300 5
0125—0208 6
1000
0385—0520 5
0261—0416 6
2000
0590—0730 5
0460—0590 6
3000
0820—1030 5
0650—0820 6
4000
1300—1450 5 (6-p)
1300—1450 6 (12-p)
6000
7000
200 mm
800 mm
11489_00