6
vacon • 50
CABLING AND CONNECTIONS
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
6.2.7.3
Low-harmonic drives
Table 18. Cable and aR fuse sizes for Vacon NX_6 low-harmonic drive
Frame
Type
I
L
[A]
Bussmann / Ferraz
Shawmut fuse type
Fuse I
n
[A]
Mains and motor
cable
1)
[mm
2
]
No of
supply
cables
No of
motor
cables
AF9
NXC0125 6
NXC0144 6
NXC0170 6
NXC0208 6
125
144
170
No additional drive fuses needed
Cu: 3*95+50
Even/Odd
Even/Odd
208
No additional drive fuses needed
Cu: 3*150+70
Even/Odd
Even/Odd
AF10
NXC0261 6
261
No additional drive fuses needed
Cu: 3*185+95
Al: 2*(3*95Al+29Cu)
Even/Odd
Even/Odd
NXC0325 6
325
No additional drive fuses needed
Cu: 2*(3*95+50)
Al: 2*(3*150Al+41Cu)
Even/Odd
Even/Odd
NXC0385 6
385
No additional drive fuses needed
Cu: 2*(3*120+70)
Al: 2*(3*185Al+57Cu)
Even/Odd
Even/Odd
NXC0416 6
416
No additional drive fuses needed
Cu: 2*(3*150+70)
Al: 2*(3*185Al+57Cu)
Even/Odd
Even/Odd
AF12
NXC0460 6
460
No additional drive fuses needed
Cu: 2*(3*150+70)
Al: 2*(3*240Al+72Cu)
Even/Odd
Even
NXC0502 6
502
No additional drive fuses needed
Cu: 2*(3*185+95)
Al: 2*(3*300Al+88 Cu)
Even/Odd
Even
NXC0590 6
590
No additional drive fuses needed
Cu: 2*(3*240+120)
Al: 4*(3*120Al+41Cu)
Even/Odd
Even
NXC0650 6
650
No additional drive fuses needed
Cu: 4*(3*95+50)
Al: 4*(3*150Al+41Cu)
Even/Odd
Even
NXC0750 6
750
No additional drive fuses needed
Cu: 4*(3*120+70)
Al: 4*(3*150Al+41Cu)
Even/Odd
Even
NXC0820 6
820
No additional drive fuses needed
Cu: 4*(3*150+70)
Al: 4*(3*185Al+57Cu)
Even/Odd
Even
AF13
NXC0920 6
920
No additional drive fuses needed
Cu:4*(3*150+70)
Al:4*(3*2405+72Cu)
Even/Odd
Even/Odd
NXC1030 6
1030
No additional drive fuses needed
Cu:4*(3*185+95)
Al:5*(3*185+57Cu)
Even/Odd
Even/Odd
NXC1180 6
1180
No additional drive fuses needed
Cu:5*(3*185+95)
Al:6*(3*185+72Cu)
Even/Odd
Even/Odd
AF14
NXC1500 6
1500
No additional drive fuses needed
Cu:6*(3*185+95)
Al:8*(3*185+57Cu)
Even/Odd
Even
NXC1900 6
1900
No additional drive fuses needed
Cu:6*(3*240+120)
Al:8*(3*240+72Cu)
Even
Even
NXC2250 6
2250
No additional drive fuses needed
Cu:8*(3*240+120)
Al:8*(3*300+88Cu)
Even
Even
1)
Based on correction factor 0.7. Cables are laid on a cable ladder side by side, three ladders on top of each
other. Ambient temperature is 30 °C (86 °F). EN60204-1 and IEC 60364-5-523.