8.2.1.1
Control cables
The control cables shall be at least 0.5 mm
2
screened multicore cables, see Table 12. The
maximum terminal wire size is 2.5 mm
2
for the relay terminals and 1.5 mm
2
for other terminals.
Find the tightening torques of the option board terminals in Table below.
8.2.1.2
Galvanic isolation barriers
The control connections are isolated from the mains potential and the GND terminals are
permanently connected to ground. See Figure 36.
The digital inputs are galvanically isolated from the I/O ground. The relay outputs are additionally
double-isolated from each other at 300VAC (EN-50178).
Figure 36. Galvanic isolation barriers
Table 20. Tightening torques of terminals
Terminal
screw
Tightening torque
Nm
lb-in.
Relay and thermistor terminals
(screw M3)
0.5
4.5
Other terminals
(screw M2.6)
0.2
1.8