fault tracing
5
8
System fault
• component failure
• faulty operation
Reset the fault and
restart.
If the fault re-occurs, con-
tact the distributor near to
you.
NOTE!
If fault F8 occurs,
find out the subcode of the
fault from the Fault His-
tory menu under Id xxx!
9
Under voltage
The DC-link voltage has gone
below the internal safety limit:
• most probable cause: supply
voltage is too low
• frequency converter internal
fault
• Power outages
In case of temporary sup-
ply voltage break reset the
fault and restart the fre-
quency converter. Check
the supply voltage. If it is
adequate, an internal fail-
ure has occurred.
Contact the distributor
near to you.
11
Output phase fault
Current measurement has
detected that there is no current
in one motor phase.
Check motor cable and
motor.
13
Frequency converter
under temperature
Heat sink temperature is under
-10
°C
Check the ambient tem-
perature.
14
Frequency converter
over temperature
Heat sink is overheated.
Check that the cooling air
flow is not blocked.
Check the ambient tem-
perature.
Clean the heatsink dust.
Make sure that the
switching frequency is not
too high in relation to
ambient temperature and
motor load.
15
Motor stalled
Motor stall protection has
tripped.
Check that the motor is
able to rotate freely.
16
Motor over tempera-
ture
Motor overheating has been
detected by frequency converter
motor temperature model. Motor
is overloaded.
Decrease the motor load.
If no motor overload
exists, check the temper-
ature model parameters.
17
Motor underload
Motor underload protection has
tripped.
Check motor and load,
e.g. for broken belts or dry
pumps.
Fault
code
Fault name
Possible cause
Correcting actions
Table 5.1: Fault codes
Содержание 20
Страница 1: ...vacon 20 ac drives complete user manual ...
Страница 2: ......
Страница 6: ...1 ...
Страница 12: ...6 vacon safety 1 ...
Страница 20: ...14 vacon installation 3 Figure 3 7 Flange mounting depth dimensions for MI4 and MI5 Unit mm MI5 MI4 ...
Страница 27: ...installation vacon 21 3 ...
Страница 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Страница 29: ...installation vacon 23 3 ...
Страница 30: ...24 vacon installation 3 ...
Страница 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 32: ...26 vacon installation 3 ...
Страница 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Страница 43: ...installation vacon 37 3 4 5 6 ...
Страница 52: ...46 vacon installation 3 ...
Страница 76: ...70 vacon control panel 7 ...
Страница 104: ...98 vacon parameters 8 ...
Страница 152: ...146 vacon parameter descriptions 9 ...
Страница 158: ...152 vacon technical data 10 ...
Страница 159: ......
Страница 160: ...Rev E2 Document ID ...