U nderload curve at
zero freq. P13.15= 10%
f
5 H z
U nderload cu rv e at
Field w eaken ing
point , P1.11
U nd e rlo ad a re a
To rq ue
Feild weakening point,
P13.14(default)=50%
parameter descriptions
vacon
•
127
9
Figure 9.16: Underload protection
13.7 M
OTOR
THERMAL
PROTECTION
0 =
No action
1 =
Alarm
2 =
Fault, stop function
3 =
Fault, coast
If tripping is selected the drive will stop and activate the fault stage, if the tem-
perature of the motor becomes too high. Deactivating the protection, i.e. set-
ting parameter to 0, will reset the thermal model of the motor to 0%.
The motor thermal protection is to protect the motor from overheating. The drive is
capable of supplying higher than nominal current to the motor. If the load requires
this high current there is a risk that the motor will be thermally overloaded. This is
the case especially at low frequencies. At low frequencies the cooling effect of the
motor is reduced as well as its capacity. If the motor is equipped with an external fan
the load reduction at low speeds is small.
The motor thermal protection is based on a calculated model and it uses the output
current of the drive to determine the load on the motor.
The motor thermal protection can be adjusted with parameters. The thermal current
I
T
specifies the load current above which the motor is overloaded. This current limit
is a function of the output frequency.
The thermal stage of the motor can be monitored on the control keypad display.
CAUTION! The calculated model does not protect the motor if
the airflow to the motor is reduced by blocked air intake grill.
Содержание 20
Страница 1: ...vacon 20 ac drives complete user manual ...
Страница 2: ......
Страница 6: ...1 ...
Страница 12: ...6 vacon safety 1 ...
Страница 20: ...14 vacon installation 3 Figure 3 7 Flange mounting depth dimensions for MI4 and MI5 Unit mm MI5 MI4 ...
Страница 27: ...installation vacon 21 3 ...
Страница 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Страница 29: ...installation vacon 23 3 ...
Страница 30: ...24 vacon installation 3 ...
Страница 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 32: ...26 vacon installation 3 ...
Страница 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Страница 43: ...installation vacon 37 3 4 5 6 ...
Страница 52: ...46 vacon installation 3 ...
Страница 76: ...70 vacon control panel 7 ...
Страница 104: ...98 vacon parameters 8 ...
Страница 152: ...146 vacon parameter descriptions 9 ...
Страница 158: ...152 vacon technical data 10 ...
Страница 159: ......
Страница 160: ...Rev E2 Document ID ...