parameter descriptions
vacon
•
105
9
After the Stop command, the speed of the motor is decelerated ac-
cording to the set deceleration parameters.
If the regenerated energy is high it may be necessary to use an exter-
nal braking resistor for to be able to decelerate the motor in accepta-
ble time.
2.4
I / O
START
STOP
LOGIC
Values 0...4 offer possibilities to control the starting and stopping of the AC
drive with digital signal connected to digital inputs. CS = Control signal.
The selections including the text 'edge' shall be used to exclude the possibility
of an unintentional start when, for example, power is connected, re-connected
after a power failure, after a fault reset, after the drive is stopped by Run En-
able (Run Enable = False) or when the control place is changed to I / O control.
The Start / Stop contact must be opened before the motor can be started.
I/O stop logic uses accurate stop mode.Accurate stop mode is that the stop
time is fixed from falling edge of DI to power stopping the drive.
Selection
number
Selection name
Note
0
CS1:Forward
CS2:Backward
The functions take place when the contacts are closed.
Figure 9.3: Start/Stop logic, selection 0
1
2
3
4
5
6
7
8
9
10
11
12
13
t
Output
frequerty
0 Hz
Set
frequerty
Set
frequerty
REV
FWD
Run enable
Ctrl signal 1
Ctrl signal 2
Keypad
start button
Keypad
stop button
Содержание 20
Страница 1: ...vacon 20 ac drives complete user manual ...
Страница 2: ......
Страница 6: ...1 ...
Страница 12: ...6 vacon safety 1 ...
Страница 20: ...14 vacon installation 3 Figure 3 7 Flange mounting depth dimensions for MI4 and MI5 Unit mm MI5 MI4 ...
Страница 27: ...installation vacon 21 3 ...
Страница 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Страница 29: ...installation vacon 23 3 ...
Страница 30: ...24 vacon installation 3 ...
Страница 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 32: ...26 vacon installation 3 ...
Страница 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Страница 43: ...installation vacon 37 3 4 5 6 ...
Страница 52: ...46 vacon installation 3 ...
Страница 76: ...70 vacon control panel 7 ...
Страница 104: ...98 vacon parameters 8 ...
Страница 152: ...146 vacon parameter descriptions 9 ...
Страница 158: ...152 vacon technical data 10 ...
Страница 159: ......
Страница 160: ...Rev E2 Document ID ...