48
•
vacon
commissioning
4
7
Perform test run
without motor
. Perform either Test A or Test B:
A)
Control from the I / O terminals:
• Turn the Start/Stop switch to ON position.
• Change the frequency reference (potentiometer).
• Check the Monitoring Menu and make sure that the value of Output fre-
quency changes according to the change of frequency reference.
• Turn the Start / Stop switch to OFF position.
B)
Control from the keypad:
• Select the keypad as the control place with par 2.1. You can also move to
keypad control by pressing Loc / Rem button or select Local control with
par 2.5.
• Push the Start button on the keypad.
• Check the Monitoring Menu and make sure that the value of Output fre-
quency. changes according to the change of frequency reference.
• Push the Stop button on the keypad.
8
Run the no-load tests without the motor being connected to the process, if possi-
ble. If this is impossible, secure the safety of each test prior to running it. Inform
your co-workers of the tests.
• Switch off the supply voltage and wait up until the drive has stopped.
• Connect the motor cable to the motor and to the motor cable terminals of
the frequency converter.
• See to that all Start / Stop switches are in Stop positions.
• Switch the mains ON.
• Repeat test 7A or 7B.
9
Perform an identification run (see par. 1.18), especially if the application requires
a high startup torque or a high torque with low speed.
10
Connect the motor to the process (if the no-load test was running without the
motor being connected).
• Before running the tests, make sure that this can be done safely.
• Inform your co-workers of the tests.
• Repeat test 7A or 7B.
Содержание 20
Страница 1: ...vacon 20 ac drives complete user manual ...
Страница 2: ......
Страница 6: ...1 ...
Страница 12: ...6 vacon safety 1 ...
Страница 20: ...14 vacon installation 3 Figure 3 7 Flange mounting depth dimensions for MI4 and MI5 Unit mm MI5 MI4 ...
Страница 27: ...installation vacon 21 3 ...
Страница 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Страница 29: ...installation vacon 23 3 ...
Страница 30: ...24 vacon installation 3 ...
Страница 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 32: ...26 vacon installation 3 ...
Страница 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Страница 43: ...installation vacon 37 3 4 5 6 ...
Страница 52: ...46 vacon installation 3 ...
Страница 76: ...70 vacon control panel 7 ...
Страница 104: ...98 vacon parameters 8 ...
Страница 152: ...146 vacon parameter descriptions 9 ...
Страница 158: ...152 vacon technical data 10 ...
Страница 159: ......
Страница 160: ...Rev E2 Document ID ...