vacon
parameter descriptions
9
This is the maximum time allowed for an underload state to exist. An internal
up/down counter counts the accumulated underload time. If the underload
counter value goes above this limit the protection will cause a trip according
to parameter P13.6). If the drive is stopped the underload counter is reset to
zero. See Figure 9.21.
Par.13.16
Trip area
Time
Underload time counter
Underload
No underl.
Trip/warning
Par.13.6
Figure 9.21: underload counter