installation
vacon
•
45
3
between each phase conductor as well as between each phase conductor and the
protective ground conductor.
The insulation resistance must be >1 MOhm.
2. Mains cable insulation checks
Disconnect the mains cable from terminals L1, L2 / N and L3 of the frequency con-
verter and from the mains. Measure the insulation resistance of the mains cable be-
tween each phase conductor as well as between each phase conductor and the
protective ground conductor. The insulation resistance must be >1 MOhm.
3. Motor insulation checks
Disconnect the motor cable from the motor and open the bridging connections in the
motor connection box. Measure the insulation resistance of each motor winding. The
measurement voltage must equal at least the motor nominal voltage but not exceed
1000 V. The insulation resistance must be >1 MOhm.
Содержание 20
Страница 1: ...vacon 20 ac drives complete user manual ...
Страница 2: ......
Страница 6: ...1 ...
Страница 12: ...6 vacon safety 1 ...
Страница 20: ...14 vacon installation 3 Figure 3 7 Flange mounting depth dimensions for MI4 and MI5 Unit mm MI5 MI4 ...
Страница 27: ...installation vacon 21 3 ...
Страница 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Страница 29: ...installation vacon 23 3 ...
Страница 30: ...24 vacon installation 3 ...
Страница 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 32: ...26 vacon installation 3 ...
Страница 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Страница 43: ...installation vacon 37 3 4 5 6 ...
Страница 52: ...46 vacon installation 3 ...
Страница 76: ...70 vacon control panel 7 ...
Страница 104: ...98 vacon parameters 8 ...
Страница 152: ...146 vacon parameter descriptions 9 ...
Страница 158: ...152 vacon technical data 10 ...
Страница 159: ......
Страница 160: ...Rev E2 Document ID ...