128
•
vacon
parameter descriptions
9
NOTE! To comply with UL 508C requirements motor over-tempera-
ture sensing is required at installation if the parameter is set to 0.
Note:
If you use long motor cables (max. 100m) together with small drives
(<=1.5 kW) the motor current measured by the drive can be much higher than
the actual motor current due to capacitive currents in the motor cable. Con-
sider this when setting up the motor thermal protection functions.
13.8 M
TP
:A
MBIENT
TEMPERATURE
When the motor ambient temperature must be taken into consideration, it is
recommended to set a value for this parameter. The value can be set between
-20 and 100 degrees Celsius.
13.9 M
TP
:Z
ERO
SPEED
COOLING
Defines the cooling factor at zero speed in relation to the point where the mo-
tor is running at nominal speed without external cooling. The default value is
set assuming that there is no external fan cooling the motor. If an external fan
is used this parameter can be set to 90% (or even higher).
If you change the parameter P1.4 (Motor nominal current), this parameter is
automatically restored to the default value.Setting this parameter does not af-
fect the maximum output current of the drive which is determined by param-
eter P1.7 alone.
The corner frequency for the thermal protection is 70% of the motor nominal
frequency(P1.2).
The cooling power can be set between 0 - 150.0% x cooling power at nominal
frequency. See Figure 9.17.
Содержание 20
Страница 1: ...vacon 20 ac drives complete user manual ...
Страница 2: ......
Страница 6: ...1 ...
Страница 12: ...6 vacon safety 1 ...
Страница 20: ...14 vacon installation 3 Figure 3 7 Flange mounting depth dimensions for MI4 and MI5 Unit mm MI5 MI4 ...
Страница 27: ...installation vacon 21 3 ...
Страница 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Страница 29: ...installation vacon 23 3 ...
Страница 30: ...24 vacon installation 3 ...
Страница 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 32: ...26 vacon installation 3 ...
Страница 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Страница 43: ...installation vacon 37 3 4 5 6 ...
Страница 52: ...46 vacon installation 3 ...
Страница 76: ...70 vacon control panel 7 ...
Страница 104: ...98 vacon parameters 8 ...
Страница 152: ...146 vacon parameter descriptions 9 ...
Страница 158: ...152 vacon technical data 10 ...
Страница 159: ......
Страница 160: ...Rev E2 Document ID ...