AUTOMATION DEVICE 
INSTALLERS MANUAL

1 - GENERAL SAFETY INFORMATION

m

 

Prior to proceeding with installation, it is essential the 

instructions be read in full, since they contain important 
information regarding safety, installation, use and 
maintenance.

AUTOMATION MUST BE IMPLEMENTED IN COMPLIANCE WITH 
THE EUROPEAN REGULATIONS IN FORCE:

EN 60204-1, EN 12445, EN 12453, EN 13241-1, EN 12635

• The installer must provide for a device (es. magnetotermical

switch) ensuring the omnipolar sectioning of the equipment
from the power supply. The standards require a separation of
the contacts of at least 3 mm in each pole (EN 60335-1).

• The plastic case has an IP44 insulation; to connect flexible or

rigid pipes, use pipefittings having the same insulation level.

• Installation requires mechanical and electrical skills, therefore it

shall be carried out by qualified personnel only, who can issue
the Compliance Certificate concerning the whole installation
(Machine Directive 2006/42/CEE, Annex IIA).

• Also the automation upstream electric system shall comply with

the laws and rules in force and be carried out workmanlike.

• We recommend to make use of an emergency button, to be

installed by the automation (connected to the control unit
STOP input) so that the gate may be immediately stopped in
case of danger.

• For correct installation of the system, we recommend following

the instructions issued by UNAC very carefully

• This instruction manual is only for qualified technicians, who

specialize in installations and automations.

• The contents of this instruction manual do not concern the end

user.

• Every programming and/or every maintenance service should

be done only by qualified technicians.

• Anything not expressly described in these instructions is

prohibited; unforeseen uses may be a source of danger to
people and property.

• Do not install the product in explosive environments and

atmospheres: the presence of inflammable gases or fumes is a
serious safety hazard.

• Do not make any modifications to any part of the automation

device, or the accessories connected to it, unless described in
this manual.

• Any other modifications will void the warranty on the product.

• The installation steps should be conducted so as to avoid rainy

weather, which can expose electronic circuits to dangerous
water seepage.

• All operations requiring the casing of the device to opened

should be performed with the control unit disconnected from
the electricity supply and with a warning notice displayed, for
example: ”CAUTION, MAINTENANCE IN PROGRESS”.

• Avoid exposing the device close to sources of heat and flame.

• In the event of interventions on automatic or differential

breakers or fuses, it is essential that faults be identified and
resolved prior to resetting. In the case of faults that cannot
be resolved using the information to be found in this manual,
consult the V2 customer assistance service.

• V2 declines all responsibility for failure to comply with good

construction practice standards in addition to structural
deformation of the gate that might occur during use.

• V2 reserves the right to make modifications to the product

without prior warning.

• Installation/maintenance personnel should wear individual

protection devices (IPDs), such as overalls, safety helmets, boots
and gloves.

• The ambient operating temperature should be that indicated in

the technical characteristics table.

• The automation device should be shut down immediately in

the event of any anomalous or hazardous situation; the fault
or malfunction should be immediately reported to the person
responsible.

• All safety and hazard warnings on the machinery and

equipment should be complied with.

• Electromechanical actuators for gates are not intended to be

used by people (including children) with diminished physical,
sensory or mental capacity, or lacking in experience or
knowledge, unless they are under supervision or have been
instructed in use of the actuator by a person responsible for
safety.

• DO NOT introduce objects of any kind into the compartment

below the motor cover.

V2 has the right to modify the product without previous 
notice; it also declines any responsibility to damage or 
injury to people or things caused by improper use or wrong 
installation.

1.1 - TECHNICAL ASSISTANCE SERVICE

For any installation problem please contact our Customer Service 
at the 39-0172.812411 operating Monday to Friday
from 8:30 to 12:30 and from 14:00 to 18:00.

Содержание ZORUS

Страница 1: ...ZIS510 IL 341 1 EDIZ 12 12 2019 ZORUS GB IRREVERSIBLE ELECTROMECHANICAL PIVOTING ARM ACTUATOR FOR SWING GATES...

Страница 2: ...165 306 250 62 46...

Страница 3: ...BONS 4 7 ACTIVATION INPUTS 4 8 STOP 4 9 LOW VOLTAGE LIGHT OUTPUT 4 10 COURTESY LIGHTS 4 11 LOCK 4 12 EXTERNAL AERIAL 4 13 PLUG IN RECEIVER 4 14 ADI INTERFACE 4 15 POWER SUPPLY 4 16 BATTERY POWER 4 17...

Страница 4: ...odifications will void the warranty on the product The installation steps should be conducted so as to avoid rainy weather which can expose electronic circuits to dangerous water seepage All operation...

Страница 5: ...are authorised for use and closure is not in a public area Examples of this type are gates inside business premises where the sole users are employees or a part of them who have been suitably informed...

Страница 6: ...Directive 2006 42 EC annex I chapter 1 Low Voltage Directive 2014 35 EU Electromagnetic Compatibility Directive 2014 30 EU Directive ROHS3 2015 863 EU The relevant technical documentation is available...

Страница 7: ...x 0 5 mm2 2 x 0 5 mm2 Photocells RX 4 x 0 5 mm2 4 x 0 5 mm2 4 x 0 5 mm2 Key switch 2 x 0 5 mm2 2 x 0 5 mm2 2 x 0 5 mm2 Flashing light 2 x 1 5 mm2 2 x 1 5 mm2 2 x 1 5 mm2 Antenna integrated into the fl...

Страница 8: ...column 2 Trace a vertical line starting from the point identified and obtain value A 3 Before proceeding with the installation make sure that value A allows to fix the rear bracket otherwise select an...

Страница 9: ...re the arm onto the gear motor using the screw 2 Fix the two arms to each other using the pin and the seger Secure the gear motor to the front bracket 1 Secure the gear motor arm to the bracket using...

Страница 10: ...e cover 3 Unscrew the screw in the motor arm and remove it 4 Fix the limit switches on the motor arm these must also be installed in the presence of mechanical stops on the ground 5 At this point re i...

Страница 11: ...of the manual relating to the Control unit 7 By screwing or unscrewing the two screws A on the motor the two limit switches can be adjusted then using the two screws B block the two adjusting screws...

Страница 12: ...s relevant menu The device can operate without mains power by using the optional battery pack code 161212 Low voltage output that can be used for a signal light or a 24V flashing light Auxiliary relay...

Страница 13: ...tive rubber edges are used the outputs should be connected in cascade and only the final edge should be terminated on the nominal resistance Active edges connected to the accessory power supply are in...

Страница 14: ...d input function can also be activated by pressing i key outside the programming menu or by means of a remote control stored on channel 2 4 8 STOP For a better safety you can fit a stop switch that wi...

Страница 15: ...G it is necessary to turn off the control unit power before doing the operations mentioned here below Pay attention to the way you connect the removable modules MR2 module receiver is provided with 4...

Страница 16: ...B2 Fuse T1 6A 230V 50Hz L N COURTESY LIGHT CONTACT RECEIVER LOCK LAMP 24V 3W 24VDC COM 24VDC Photo TX Edge Test START P STOP COM PHOTO PHOTO I EDGE1 EDGE2 COM BATTERY START ANT M2 M1 Max 500mA 24 Vdc...

Страница 17: ...IN PROGRESS OPENED CONTACT CLOSED CONTACT START PEDESTRIAN START PAUSE GATE OPENED CLOSING IN PROGRESS SAFETY RIBBON 2 OK STOP EXTERNAL PHOTOCELL INTERNAL PHOTOCELL SAFETY RIBBON 1 The control panel...

Страница 18: ...ening direction 4 Verifying Slave motor connection 5 Self training the working times mWARNING Ensure that the motors and accessories are connected correctly prior to performing initialisation Position...

Страница 19: ...tor press OK to move to the next phase If the installation envisages two motors select the doP menu option and press OK The display will show Er94 to indicate that the SLAVE motor is not connected or...

Страница 20: ...times dEF Loading the default parameters ini Control unit initialisation 8 RAPID CONFIGURATION Rapid configuration is a menu allowing the main control unit parameters to be programmed with a few opera...

Страница 21: ...stopped when one of the following conditions is present During slowing During the first work cycle after accessing the programming menu After having powered up the control unit This menu option is use...

Страница 22: ...from the beginning During closure a Start command immediately reopens the gate 8 4 EXITING RAPID CONFIGURATION This menu closes programming both predefined and customised saving the modified data in t...

Страница 23: ...alisation procedure is performed even without working time self training The parameters acquired during initialisation are maintained even when the default parameters are loaded 1 Press and hold the O...

Страница 24: ...point for gate leaf 1 4 4 An opening manoeuvre is performed for each gate leaf the operation terminates when one of the conditions described in part 4 2 occurs the first START stops gate leaf 1 the s...

Страница 25: ...play of thousands or units Area 2 is the reading of the number of cycles before the next request for service its value is rounded down to the hundreds Area 3 is the setup of this latter counter if you...

Страница 26: ...to the length of time set by this menu adjustable time from 0 0 to 1 00 t SEr Lock time 2 0 0 5 1 00 Before the opening phase begins the control unit will energize the electric lock in order to releas...

Страница 27: ...30 100 The displayed value is the percentage of max motor power Pot2 Motor 2 power 100 30 100 The displayed value is the percentage of max motor power Po r1 Power Motor 1 during slow down phase 30 0...

Страница 28: ...n this menu it is possible to adjust the duration of the braking phase The value set is the percentage of the total trip and is equal for both motors during opening and closing St AP Start command dur...

Страница 29: ...ic working is enabled the time of the pause is Ch tr LUCi Courtesy lights This menu allows setting the automatic operating of the courtesy lights during the opening cycle of the gate NOTE If the outpu...

Страница 30: ...sing phase only Warning if you select this option you must disable photocell test Fot i Interior photocell input This menu makes it possible to enable the interior photocell input i e active during op...

Страница 31: ...Motor Release on Mechanical Stop When the gate halts against the mechanical stop the motor is controlled for a fraction of a second in the opposite direction decreasing the motor gear tension 2 0 Func...

Страница 32: ...een set correctly Check that the safety edges enabled from the menu are installed Error 8 When executing a self learning function the control is refused and the display shows Err8 It means that the se...

Страница 33: ...ENGLISH 65...

Страница 34: ...self as well as to human health As indicated by the symbol opposite throwing away this product as domestic waste is strictly forbidden So dispose of it as differentiated waste in accordance with your...

Страница 35: ...ntenance as with all machinery your automation devices requires periodic maintenance so that it may continue to work for as long as possible and in complete safety Agree a periodic maintenance plan wi...

Страница 36: ...ENGLISH 68...

Страница 37: ......

Страница 38: ......

Отзывы: