ENGLISH
- 40 -
19 - CONTROL MODE FROM TERMINAL
BOARD
To control the door through external devices you need have to
connect devices with normally open contact between terminals
S1-S4
,
S2-S4
or
S3-S4
and set for each the desired function via
the parameters
ING1
,
ING2
and
ING3
.
The functions available are:
•
Start
(
START
value to be set)
This function corresponds to a generic activation command
and controls the following operations:
- When the door is closed, an opening cycle starts
- When the door is opening depends on the setting of
parameter
ST.AP:
NO
: command not active
CHIU
: the door closes immediately
PAUS
: the door stops (if the automatic closing mode is
on the pause time counting starts)
- When the door is open and the pause the counting is not
active, the closing starts
- When the door is open and the pause time counting is
active, depends on the menu
ST.PA
:
NO
: command not active
CHIU
: closing starts
PAUS
: reset the pause time counting
- When the door is closing depends on the menu
ST.CH
:
APRE
: the door re-opens
STOP
: the door will stop and the cycle is considered
finished
- When the door is stopped due to a stop command or the
detection of an obstacle, a command Start restarts the
door in the same direction as it was before being stopped.
If the parameter
STOP
is set to
INVE
the door again
moves, but in the opposite direction.
- When the door began a partial opening cycle commands a
total opening
•
Partial start
(value to be set
ST.PE
)
This function corresponds to a partial opening command
and controls the following operations:
- When the door is closed, a partial opening cycle starts;
the door opens only for the percentage of travel set in the
parameter
P.APP
, or until the contact connected to
terminal
H4
opens (
ENCO
parameter set on
INTRM
)
Once you start the cycle, the functions are those described
the
START
command.
- When the door began a normal opening cycle this
command has no effect.
•
Stop
(
STOP
value to be set)
This function corresponds to a stop command: it is the only
case in which the connected device must work with normally
closed contact; it can be used to stop the door and hold it in
a locked position.
The operation of the STOP command depends on the value
set for the parameter
STOP
:
-
PROS
: the door stops in its current position and as long
as the contact is open no command is effective.
Once the contact is closed again, any start command
restarts the door that follows its previous direction.
-
INVE
: the door stops in its current position and as long
as the contact is open no command is effective.
Once the contact is closed again, any start command
restarts the door in the opposite direction.
-
APRE
: the door stops any movement and opens
completely. If an active safety device prevents the opening,
the door does not move until the device involved is
deactivated, then it opens. So the door remains locked in
the open position until the STOP contact closes again.
-
CHIU
: the door does not stop the movement immediately,
but when it stops it closes.
If a safety device causes its re-opening, the operation is
carried out, then again closing is commanded.
When the door is closed, it remains locked in this position
until the STOP contact is closed again.
•
Always opens
(
APRE
value to be set)
Always controls the opening, regardless of the position of the
door, if the door is already open, it is ineffective.
NOTE
: This command is not available for the input ING3.
•
Always closes
(
CHIU
value to be set)
Always control the closing: if the door is already closed it is
ineffective.
NOTE
: This command is not available for the input ING3.
•
Force dead man mode
(
PRES
value to be set)
This command is available only on the input ING3: when the
contact is closed the unit is operating in dead man mode.