ENGLISH
- 48 -
PARAMETER
VALUE
DESCRIPTION
AntE SCor
MEMO
t.CvE
Fast closing time after slowing down
0.0” 0.0”
0.0” - 5.0”
If a slowing time other than 0 is set up, it could be likely that the gate
speed is not enough for the lock to fasten during the closing phase.
In case this function is enabled, once the slowing down phase is
finished, the control unit will give a normal speed command (that is to
say, with no slowing down) for the set up time, and then it will open
the gate for a second fraction, to avoid leaving the motor under stress.
m
PLEASE NOTE:
Set to
0
if the gate is not fitted with electro-
locks or if slowing is disabled.
tE.M
Enabling the test motor
The unit performs an operation test on the motor before starting the
automation.
ATTENTION:
disable this function only if it is necessary to perform
emergency manoeuvres.
Si
Si
Si
Function activated
no
Function deactivated
St.AP
Start command during the opening phase
This menu allows fixing the control unit conduct in case it receives a
Start command during the opening phase
PAUS PAUS
PAUS
The gate stops and goes to pause
ChiU
The gate immediately starts closing
no
The gate go on with the opening phase (command is ignored)
St.Ch
Start command during the closing phase
This menu allows fixing the control unit conduct in case it receives a
Start command during the closing phase
StoP StoP
StoP
The gate stops and its cycle is considered as finished
APEr
The gate opens again
St.PA
Start command during the pause
This menu allows fixing the control unit conduct in case it receives a
Start command when the gate is open during its pause phase
ChiU ChiU
ChiU
The gate starts closing
no
Command is ignored
PAUS
The pause time is reset (
Ch.AU
)
SPAP
Pedestrian Start during the partial opening phase
This menu allows fixing the control unit conduct in case it receives a
Pedestrian Start command during the partial opening phase.
m
WARNING
: a Start command in any phase of partial opening
will cause the total opening; the Start Pedestrian command is always
ignored during a total opening.
PAUS PAUS
PAUS
The gate stops and goes to pause
ChiU
The gate immediately starts closing
no
The gate goes on with the opening phase (command is ignored)
Ch.AU
Automatic closing
no
no
no
Function deactivated
0.5” - 20.0’
The gate closes after the setup time