6 - PLUG IN RECEIVER

CITY4-EVO is suitable for plugging in a Personal Pass MR receiver.

m

 

WARNING: Pay attention to the way you connect the 

removable modules.

MR1 module receiver is provided with 4 channels and each of 
them is suitable for a command of CITY4-EVO control unit::
•  CHANNEL 1 

g

 START

•  CHANNEL 2 

g

 PEDESTRIAN START

•  CHANNEL 3 

g

 STOP

•  CHANNEL 4 

g

 COURTESY LIGHT

The transmitter codes can be stored in two ways:

1.

  By pressing the P1 button on the MR receiver (read the 

instructions supplied with the receiver)

2.

  Using WINPPCL software: to run the program you need to 

connect a PC to the control unit. The connection can be made 
via USB using a standard USB cable.

7 - USB CONNECTOR

The CITY4-EVO unit is equipped with an USB connector for 
connection with a PC.
By using software V2+ (version 2.0 or higher), it is possible to 
carry out the following operations: 

1.

  Firmware update of the unit.

2.

  Change of programming parameters. 

3.

  Reading information of diagnostics. 

If the unit is not fed, by connecting the USB cable to the unit and 
the PC, the display switches on and caption 

-USb

 is displayed: in 

this stage only the programming operations through the PC can 
be carried out.

If the unit is fed, by connecting the USB cable to the unit and the 
PC, the display continues to display the control panel: in this stage 
the programming operations through the PC, can be carried out, 
or control the gate.

NOTE: to carry out the firmware updating, it is necessary to 
disconnect the unit network power supply 

(during updating 

the display is switched off).

All other operations can be carried out while the unit is 
power supplied.

5.13 - EXTERNAL AERIAL

We suggest to use the external aerial (model: ANS433) in order to 
guarantee the maximal range.

Connect the antenna hot pole to terminal 

L1

 of the control unit 

and the braiding to terminal 

L2

.

L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11

5.14 - POWER SUPPLY

The control unit must be fed by a 230V - 50Hz (120V - 50/60Hz
for 120V model) electric line, protected by a differential 
magnetothermal switch complying with the law provisions in 
force.

Connect power supply cables to terminals 

L

 and 

N

.

N

230V - 50Hz

L

Содержание CITY4-EVO

Страница 1: ...DIGITALE UNIVERSALE PER IL COMANDO DI UN MOTORE 230V 120V UNIVERSAL DIGITAL CONTROL UNIT FOR THE CONTROL OF A 230V 120V ENGINE CENTRALE DIGITALE UNIVERSELLE POUR LE CONTROLE D UN MOTEUR A 230V 120V CU...

Страница 2: ...DOWN MENU UP MAINS OVERLOAD J1 J2 J3 FISSAGGIO FIXING FIXATION FIJACION...

Страница 3: ...T 5 12 LOCK 5 13 EXTERNAL AERIAL 5 14 POWER SUPPLY 6 PLUG IN RECEIVER 7 USB CONNECTOR 8 ADI INTERFACE 9 CONTROL PANEL 9 1 USE OF DOWN MENU AND UP KEYS FOR PROGRAMMING 10 QUICK CONFIGURATION 11 LOADING...

Страница 4: ...ly who can issue the Compliance Certificate concerning the whole installation EEC Machine Directive 89 392 Annex IIA The automated vehicular gates shall comply with the following rules EN 12453 EN 124...

Страница 5: ...efore each opening as required by the referred regulations Deactivation of safety inputs through the configuration menu no jumper is required for terminals concerning safety devices that have not been...

Страница 6: ...24 Vac for photocells and other accessories Z2 Common for accessories power supply Z3 Photocell optical edge TX power supply for functional test Z4 Z5 Lock 12V Z5 Z6 Low voltage light 12Vdc 3W RM MR...

Страница 7: ...NTACT FLASHING LIGHT ANT DOWN MENU UP MAINS Z1 Z2 Z3 Z4 Z5 Z6 G1 G2 G3 G4 G5 G6 G7 N L OPEN COM CLOSE M OVERLOAD J1 J2 J3 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 mATTENTION jumpers J1 and J2 must be remove...

Страница 8: ...mode DEFAULT START START it controls the total opening of the gate START P START PEDONALE it controls the partial opening of the gate Open Close command START APERTURA it controls the opening of the...

Страница 9: ...ns of a remote control stored on channel 1 see relevant instructions of MR receiver The START P function can also be activated by pressing DOWN key outside the programming menu or by means of a remote...

Страница 10: ...L9 and L11 closing limit switch in door 1 between terminal L10 and L11 FCC FCA L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 5 8 ENCODER With CITY4 EVO you can use encoder equipped motors to control the exact po...

Страница 11: ...when a remote control arrives on channel 4 and opens after the time set If a second remote control reaches channel 4 before the time is up the relay opens 5 11 LOW VOLTAGE LIGHT The control unit has a...

Страница 12: ...nostics If the unit is not fed by connecting the USB cable to the unit and the PC the display switches on and caption USb is displayed in this stage only the programming operations through the PC can...

Страница 13: ...e is added or removed it is necessary to repeat the scanning procedure in order to update the unit 9 CONTROL PANEL When power is on the control unit checks that display correctly operates by switching...

Страница 14: ...ss the DOWN key the display shows SCor 4 Press the MENU key no will appear on the display 5 Press the DOWN key Si will appear on the display 6 Press the MENU key All of the parameters are returned to...

Страница 15: ...lay will show ESC press the MENU key only if you want to leave this menu 3 Press the DOWN key t LAv will appear on the display 4 Press the MENU key to start the self learning cycle for the work cycle...

Страница 16: ...t service request Area 1 is the reading of the total number of completed cycles through Up and Down keys you can alternate the display of thousands or units Area 2 is the reading of the number of cycl...

Страница 17: ...ending order from n 01 to n 32 select the event and press the MENU key to display the following information A EVENT CODE The code displayed is used to define the type of event that has occurred see th...

Страница 18: ...n of the COST safety strip 2 3 4 CoSt E059 Activation of the virtual safety strip control from an ADI device 2 3 4 i Adi E066 Intervention of the amperometric protection on opening 2 SEnS E067 Interve...

Страница 19: ...out changes and going back to the control unit normal operation You must exit from programming mode through this menu item if you do not want to lose your configuration mWARNING in case no operation i...

Страница 20: ...d to setup a longer time than t AP opening time t APP Partial opening time pedestrian access 6 0 6 0 0 0 2 00 When the control unit receives a Start Pedestrian command it will open leaf for a shorter...

Страница 21: ...off When the gate is standstill and it begins moving the initial inertia must be faced therefore if your gate is quite heavy it could not move In case the SPUNTO pickup function is activated for the f...

Страница 22: ...The gate stops and goes to pause ChiU The gate immediately starts closing no The gate go on with the opening phase command is ignored St Ch Start command during the closing phase This menu allows fixi...

Страница 23: ...unction disabled t LUC Operation timed from 0 0 to 20 0 1 00 1 00 CiCL Lights on for the entire duration of the cycle AUS Auxiliary Channel This menu allows you to set relay operation for courtesy lig...

Страница 24: ...Photocells Input This menu allows input to be enabled for the photocells CFCh CFCh APCh Input enabled on opening and closure CFCh Photocell active on closure and with gate stopped Ch Input enabled for...

Страница 25: ...if the limit switch is enabled the START ON OPENING must be disabled St AP parameter no mWARNING Improper use of this function can affect the safety of using the automation V2 recommends Use this func...

Страница 26: ...the unit detects the devices During scanning the display shows the number of detected devices Once scanning is completed the display shows ESC select ESC to exit from the menu without programming the...

Страница 27: ...turn exactly to the starting position it is possible to set an anti skid time that is added to the time calculated by the control unit in order to recover the inertia mWARNING If function ASM is disab...

Страница 28: ...errors detected by the various tests Err2 Err3 etc 2 Even the events that change the normal operation of the gate coming into action of a safety control by user etc 3 Even the safeties that have prev...

Страница 29: ...mand is given the gate won t open It means that intervention of safety edge prevents gate movement 1 Check the safety edge is not pressed or damaged 2 Ensure safety edge is connected correctly activat...

Страница 30: ...hows Err5 When a start command is given the gate won t open It means that the test of the safety edges failed 1 Make sure that the menu relative to the test of the facets for cables Co tE is configure...

Страница 31: ...V2 S p A Corso Principi di Piemonte 65 67 12035 RACCONIGI CN ITALY Tel 39 0172 812411 Fax 39 0172 84050 info v2home com www v2home com...