PARAMETER
VALUE
DESCRIPTION
AntE SCor
MEMO
ShAd
Shaded area of the photocell
In some installations due to the garage, it is possible that the door
gets in front of the photocells, interrupting the beam. If this is the
case, the door cannot complete the closing cycle.
With this function, it is possible to temporarily disable photocells
during the closing phase, so as to allow clear passage of the door.
The photocells are deactivated when the door exceeds the stroke
percentage set for the
F.ShA
limit (end of shaded area) and are
re-activated when the door exceeds the stroke percentage set for the
i.ShA
limit (start of shaded zone).
The limits of the shaded area are set automatically during the self-
learning cycle (Chapter 12), as the function has been previously
enabled by setting any value for the
i.ShA
and
F.ShA
limits
(including
0
).
m
NOTE: this function can only be activated if the following
conditions are met:
• encoders or limit switches must be enabled
• if the limit switch is enabled, the START ON OPENING must be
disabled (
St.AP
parameter =
no
)
m
WARNING: Improper use of this function can affect the
safety of using the automation. V2 recommends:
• Use this function only when the passage of the door in front of the
photocell really is inevitable.
• Set the closest possible shaded area limits
no
no
no
Function deactivated
F.ShA
0 - 100
End of the shaded area: the photocells are deactivated when the
door exceeds the stroke percentage set (
0
= door closed /
100
= door
open)
i.ShA
0 - 100
Start of the shaded area: the photocells are re-activated when the
door exceeds the stroke percentage set (
0
= door closed /
100
= door
open)
CoSt
Sensitive Rib Input
This menu allows input to be enabled for the sensitive ribs
no
no
no
Input disabled
APCh
Input enabled in opening and closure
Ch
Input enabled during the closing and disabled during the opening
AP
Input enabled during the opening and disabled during the closure
Co.tE
Test of the safety edges
This menu allows setting the method of control of the safety edges
working
no
no
no
Test disabled
rESi
Test enabled for conductive rubber safety edges
Foto
Test enabled for optical safety edges