V2 CITY1 Скачать руководство пользователя страница 20

E

N

G

L

IS

H

43

READING OF CYCLE COUNTER

CITY1

control unit counts the completed opening cycles of the

gate and, if requested, it shows that service is required after a
fixed number of cycles.

There are two counters available:
• A totalizing counter for completed opening cycles that 

cannot be zeroed (option “

tot

” of item “

Cont

”)

• A downward counter for the number of cycles before the 

next request for service (option “

SErv

” of item “

Cont

”). This 

counter can be programmed according to the desired value.

The side scheme shows how to read the totalizing counter, how
to read the number of cycles before the next service is required as
well as how to program the number of cycles before the next
request for service (as for the example shown, the control unit
completed no. 12451 cycles and there are no. 1322 cycles before
the next service request.

Area 1

is the reading of the total number of completed cycles;

through Up and Down keys, you can alternate the display of
thousands or units.

Area 2

is the reading of the number of cycles before the next

request for service: its value is rounded down to the hundreds.

Area 3

is the setup of this latter counter; if you press once UP or

DOWN key, the current counter value will be rounded up or
down to thousands, any following pressure will have the setup
be increased or decreased of 1000 units. The previous 
displayed count will get lost.

Signal of service required 

As soon as the counter of cycles before the next request for
service is zero, the control unit shows the request for service
through an additional 5-second pre-blinking.

WARNING:

service operations shall be carried out by 

qualified staff only. This signal will be repeated at each 
opening cycle, until the installer enters into the counter reading
and setup menu, and possibly programs the number of cycles
after which the next service will be requested.
In case no new value is setup (that is to say that the counter
value is left at zero), the signalling function for the service 
request will be disabled and no signal will be repeated anymore.

OBSTACLE SENSOR OPERATION

CITY1

control unit is equipped with a sophisticated system that

allows detecting if there is any obstacle stopping the door
motion. The sensitivity of this system can be adjusted through
the 

Sens

menu: the higher is the setup value, the prompter will

be the control unit intervention if there is any obstacle. If you set
on 0, obstacle detection will be disabled.

WARNING:

apart from any setup sensitivity value, this

system will detect an obstacle only if the door is stopped; 
therefore, no obstacle braking the door without stopping it will
be detected. In addition, this system does not work when the
doors moves at slowed down speed.

The control unit reaction in case an obstacle is detected depends
on the 

t.rAL

menu setup and on the moment when such

obstacle is detected.

Slowing down disabled

The door motor on which an obstacle is detected will stop 
pushing and, for a second fraction, it will be given the 
command to go backwards, so not to keep its gears under stress.
If 

t.SEr

menu is set to ‘

no

’ (that is to say, no electric lock) and an

obstacle is detected during the last 3 seconds of the closing
phase, there will be no reversal, to allow the gate completing its
closing.

Slowing down enabled

Obstacle detection will be performed only if the door moves at a
normal speed. Both doors will stop and they will be given the
command to go backwards for 3 seconds, to take out the
obstacle detected. The following Start command will let the 
former door motion start again. In case the slowing down phase
has already begun, no obstacle will be detected and this kind of
situation cannot be considered as dangerous since the motor,
when working according to its slowing down function, will push
the obstacle with a very low pressure.

Содержание CITY1

Страница 1: ...IL n 170 1 EDIZ 04 03 2009 V2 S p A Corso Principi di Piemonte 65 67 12035 RACCONIGI CN ITALY tel 39 01 72 81 24 11 fax 39 01 72 84 050 info v2home com www v2home com CITY1 I...

Страница 2: ...Y RIBBONS 28 LOCK 28 END OF STROKE 28 ENCODER 28 STOP 28 ACTIVATION INPUTS 29 EXTERNAL AERIAL 29 PLUG IN RECEIVER 29 OPTIONAL MODULES 29 CONTROL PANEL 30 USE OF DOWN MENU AND UP KEYS FOR PROGRAMMING 3...

Страница 3: ...N 12453 allows We recommend to make use of an emergency button to be installed by the automation connected to the control unit STOP input so that the gate may be immediately stopped in case of danger...

Страница 4: ...d in case of disabled obstacle sensor is described WARNING In case it has not yet fitted a start capacitor for each motor is required connect the start capacitor for motor 1 between terminals 27 and 2...

Страница 5: ...good closing of doors Make use of a 12V lock Connect lock cables to terminals 20 and 21 of the control unit END OF STROKE CITY1 control unit supports the two following kinds of end of stroke end of s...

Страница 6: ...f device controlling the first input between terminals 3 and 6 of the control unit Connect cables of device controlling the second input between terminals 4 and 6 of the control unit The first input f...

Страница 7: ...nto its closing phase If it blinks it means that the closing has been caused by a safety device border or obstacle detector USE OF DOWN MENU AND UP KEYS FOR PROGRAMMING Control unit time and function...

Страница 8: ...the doors will be activated in closing direction until the stop end or the closing end of stroke is reached Be sure that the leaves do not overlap In case NEITHER the ends of stroke NOR the obstacle s...

Страница 9: ...ning phase before the relevant time expires WARNING if motor 2 is not connected this time must be set to zero in this circumstance the control unit will not consider all configurations of motor 2 and...

Страница 10: ...mmand it will use this time to close the gate Max allowed time to be setup is t CH1 To avoid that the door does not close completely we recommend to setup a longer time than t APP opening time Leaf 2...

Страница 11: ...motors to help the electric lock release The control unit controls the motors in reduced power in closing direction for the setup time The backlash precedes the electric lock release It is possible t...

Страница 12: ...down function in order to measure both opening and closing times and to enable it again once the setup has been carried out The control unit will automatically consider the working time delay caused b...

Страница 13: ...the step by step operation logic Select option APEr to set up the always open operation logic Start command during the pause This menu allows fixing the control unit conduct in case it receives a Sta...

Страница 14: ...n is disabled by setting the value to zero no will be displayed the gate can be closed through the start command only in this case St PA menu setup will be ignored If the control unit receives a Stop...

Страница 15: ...ns associated to the command of STOP no The input STOP is not available ProS The input STOP stops the gate pressing the command START the gate continues the motion invE The command STOP stops the gate...

Страница 16: ...In some installations it may occur that the gate door passes before the photocells so breaking their beam In this case the gate cannot complete its closing cycle Through this function photocells can...

Страница 17: ...eached its position of complete opening or closing no End of stroke inputs are disabled Si End of stroke inputs are enabled Motor Release on Mechanical Stop When the gate halts against the mechanical...

Страница 18: ...exactly to the starting position it is possible to set an anti skid time that is added to the time calculated by the control unit in order to recover the inertia WARNING If function ASM is disabled t...

Страница 19: ...d the learning cycle starts WARNING The procedure of the operation time automatic learning can be starter only if the Start inputs are set up on the STANDARD mode StAn End of Programming This menu all...

Страница 20: ...cles after which the next service will be requested In case no new value is setup that is to say that the counter value is left at zero the signalling function for the service request will be disabled...

Страница 21: ...0 no Pre flashing disabled it corresponds to 0 Pot1 30 100 Motor 1 power 60 60 Pot2 30 100 Motor 2 power 60 SPUn no Si Start off no Si t P So 0 5 3 0 Slowed down starting time 1 5 no no Slowed down s...

Страница 22: ...no no no Function disabled F ShA FOTO2 disabling higher time i ShA FOTO2 disabling lower time CoS1 no Si Border 1 input fixed border no no CoS2 no Si Border 2 input mobile border no no FC En no Si En...

Страница 23: ...ing phase N C contact 16 Common 17 18 Power output 24 VAC for photocells and other accessories 18 19 Photocell TX power supply for functional test 20 21 Electric lock 12VAC 22 23 Flashing light 230VAC...

Страница 24: ...K 2 x 1 5 mm2 PG9 For cables with external from 5 to 8 mm OTHER WIRINGS MULTIPOLAR n x 0 25 0 5 mm2 n depending on the number of wirings to be made PG9 For cables with external from 5 to 8 mm PG11 For...

Страница 25: ...sure that photocells are powered and working when you interrupt their beam you should hear the relay tripping Error 4 After few centimeters during the opening phase the gate stops and the display show...

Страница 26: ...V2 S p A Corso Principi di Piemonte 65 67 12035 RACCONIGI CN ITALY tel 39 01 72 81 24 11 fax 39 01 72 84 050 info v2home com www v2home com...

Отзывы: