6. TROUBLESHOOTING
IMPORTANT
All troubleshooting is to be performed by qualified personnel. Be aware of pressurized system components as some of
the troubleshooting procedures require system components to be pressurized.
Failure to do so can result in system
damage and/or personal injury.
SYMPTOM
INDICATION(S)
PROBLEM
SOLUTION
MANUAL
REFERENCE
Compressor does not
run
Green power indicator
is
OFF
ON / OFF Selector
Switch on Model SC-W
assembly is
OFF
Move ON / OFF
Selector Switch to
ON
position
4.2
Power from panelboard
is
OFF
Check circuit
breaker
Green power indicator
is
ON
Possible compressor
overheating
Allow compressor to
cool
Nitrogen purity in
sprinkler system not
increasing
Red “SYSTEM
BYPASSED
” indicator
is
ON
Model SC-W assembly
is in Bypass mode
Verify position of
valves has been
restored to Nitrogen
position.
Figure 34
Red “SYSTEM
BYPASSED” indicator
is
OFF
Model SC-W assembly
may not be producing
nitrogen
Check nitrogen
purity at test port by
using Model NA-2
analyzer
5.2.1
Model SC-W assembly
is producing 98%
nitrogen when
checked with Model
NA-2 analyzer
Valve
2
on Model SC-W
assembly is
CLOSED
Open valve
Valve on Model PVA is
CLOSED
Open valve
Model PVA assembly
has been flooded with
water
Drain Model PVA
assembly
5.4.5
Strainer at Model PVA is
clogged
Replace strainer
5.4.6
Model SC-W assembly
NOT
producing 98%
nitrogen when
checked with Model
NA-2 analyzer
Contact
UNITED
Fire Systems
Excessive compressor
runtime (more than 2-
1/2 hours per day)
during purging
During purging, the Model SC-W assembly compressor is supplying air to make nitrogen for
purging. Runtime during purging will be much greater during purging, and “excessive”
runtime is normal. Air compressor runtime should be assessed after purging is complete.
Содержание Nitrogen Pac SC-W
Страница 2: ... THIS SURFACE DELIBERATELY LEFT BLANK ...
Страница 81: ...Page 1 of 6 Model NA 2 Nitrogen Analyzer Hand Held OPERATING MANUAL INSTRUCTIONS FOR USE R218M06 Industrial ...
Страница 102: ...APPENDIX F SC W MANUAL ...
Страница 103: ...APPENDIX F SC W MANUAL ...
Страница 104: ...APPENDIX G SC W MANUAL ...
Страница 111: ... THIS SURFACE DELIBERATELY LEFT BLANK ...