3. INSTALLATION
IMPORTANT
The installation of the
NITROGEN-
PAC™
Model SC-W Sprinkler Corrosion Inhibiting System MUST be in accordance
with this manual. Read this manual in its entirety BEFORE beginning installation of the
NITROGEN-
PAC™
Model SC-
W system. Understand and follow all instructions provided in this manual.
WARNING
The Model SC-W assembly creates a 30% to 40% oxygen concentration exhaust that may present a flammability
hazard. Ensure the Model SC-W assembly is NOT located in an area where and oxygen-enriched atmosphere will be
a hazard. Failure to comply with this warning can result in increased risk from fire, including death, serious personal
injury and property damage.
CAUTION
Understand and follow all safety recommendations when moving heavy pieces of equipment. Equipment may be easily
tipped over when moving. Failure to use caution can result in equipment damage and personal injury.
IMPORTANT
Adequate ventilation is important for the
Model SC-W assembly. While natural ventilation or existing openings may be
adequate, consideration should be given to providing additional ventilation when locating the Model SC-W assembly in
a closet or other small space. A louvered door or 1-1/2 inch gap between the door and floor should be sufficient.
Check with the owner and local codes before modifying any door
.
Содержание Nitrogen Pac SC-W
Страница 2: ... THIS SURFACE DELIBERATELY LEFT BLANK ...
Страница 81: ...Page 1 of 6 Model NA 2 Nitrogen Analyzer Hand Held OPERATING MANUAL INSTRUCTIONS FOR USE R218M06 Industrial ...
Страница 102: ...APPENDIX F SC W MANUAL ...
Страница 103: ...APPENDIX F SC W MANUAL ...
Страница 104: ...APPENDIX G SC W MANUAL ...
Страница 111: ... THIS SURFACE DELIBERATELY LEFT BLANK ...