3.10. (Optional) Corrosion Monitor Assembly Model CMA-1.
Refer to
Figure 32
. Proper Model CMA-1 installation is
based on the orientation of the pipe at the intended installation location. The Model CMA-1 can be installed
horizontally in a vertical riser or branch line; and can be installed horizontally or vertically in a horizontal sprinkler
main or branch line. The assembly should be located at an accessible point for future maintenance.
IMPORTANT
DO NOT disassemble Corrosion Monitor Assembly to install! The union (refer to
Figure 32
) may be used to facilitate
installation.
3.10.1. Attachment To Sprinkler Piping.
Confirm that sprinkler piping system is
NOT
pressurized.
CAUTION
Failure to confirm that the sprinkler piping is
NOT
pressurized could result in personal injury and / or property damage.
3.10.2. Vertical Installation.
Refer to
Figure 32
. Install tee and nipple as shown. Position the tee with the outlet vertical,
as indicated. Attach Corrosion Monitor Assembly to nipple. It is acceptable to install additional pipe and elbows
before the assembly to accommodate proper installation. The assembly MUST be installed as shown for drain
valve to function properly. Use union to facilitate installation and proper assembly positioning. Isolation ball valve
should remain closed until commissioning. Follow instructions provided with replacement probe kit (UFS P/N: 30-
500013-100) when replacement is required.
3.10.3. Horizontal Installation.
Refer to
Figure 32
. Install tee and nipple, as shown. Position the tee with the outlet
horizontal, as indicated. Install a pipe nipple into the tee before the elbow, as shown. Attach Corrosion Monitor
Assembly to nipple. It is acceptable to install additional pipe and elbows before the assembly to accommodate
proper installation. The assembly MUST be installed as shown for drain valve to function properly. Use union to
facilitate installation and proper assembly positioning. Isolation ball valve should remain closed until
commissioning. Follow instructions provided with replacement probe kit (UFS P/N: 30-500013-100) when
replacement is required.
Содержание Nitrogen Pac SC-W
Страница 2: ... THIS SURFACE DELIBERATELY LEFT BLANK ...
Страница 81: ...Page 1 of 6 Model NA 2 Nitrogen Analyzer Hand Held OPERATING MANUAL INSTRUCTIONS FOR USE R218M06 Industrial ...
Страница 102: ...APPENDIX F SC W MANUAL ...
Страница 103: ...APPENDIX F SC W MANUAL ...
Страница 104: ...APPENDIX G SC W MANUAL ...
Страница 111: ... THIS SURFACE DELIBERATELY LEFT BLANK ...