UNITED FIRE SYSTEMS
NITROGEN-
PAC™
MODEL SC-W
INSTALLATION, COMMISSIONING, AND MAINTENANCE MANUAL
REVISION 1.01 MAR 2021 - P/N 30-NPWICM-000
48
Figure 30
Purge Vent Assembly Model PVA - Dimensions and Installation in Vertical Piping
3.7.4 Connection to Horizontal Piping.
Refer to
Figure 30
. Confirm that sprinkler piping system is
NOT
pressurized.
CAUTION
Failure to confirm that the sprinkler piping is
NOT
pressurized could result in personal injury and / or property damage.
(a)
Install tee and nipple in horizontal piping. Position the tee with the outlet vertical, as indicated.
(b)
Attach Purge Vent Assembly to nipple. It is acceptable to install additional pipe and elbows before the assembly to
accommodate proper installation. The assembly MUST be installed vertically as shown for float valve to function
properly. Use union to facilitate installation and proper assembly positioning.
(c)
Ball valve should remain closed until commissioning.