UNITED FIRE SYSTEMS
NITROGEN-
PAC™
MODEL SC-W
INSTALLATION, COMMISSIONING, AND MAINTENANCE MANUAL
REVISION 1.01 MAR 2021 - P/N 30-NPWICM-000
36
3.2.5 Drain Connection.
IMPORTANT
Local regulations may require the installation of an oil / water separator in condensate drain piping. Verify local
requirements before completing installation.
UNITED
Fire Systems
does not supply oil / water separators.
(a) Drain Piping.
All points on the Model SC-W assembly requiring drainage are connected to one point. Install drain
piping from Model SC-W drain connection to an appropriate drain location. Refer to
Figure 2
for location of drain
connection. Drain run may be pipe or tubing. Consult with relevant Authorities Having Jurisdiction, local codes, or
building owner for approved materials and discharge location.
(b)
Condensate Pump (Installer provided option)
. A condensate pump may be needed if drain is above the Model
SC-W assembly drain outlet, or if drain is some distance from the Model SC-W installation location.
UNITED
Fire
Systems
does not supply condensate pumps. It is recommended that this drain be run to a building drain or an
environmentally-approved condensate collection / disposal system.
(c) Oil / Water Separator (Installer provided option).
If run to a building drain, environmental regulations may
require installation of an oil / water separator.
3.2.6 Electrical Connections.
DANGER
RISK OF ELECTROCUTION
Voltages and currents associated with the Model SC-W assembly are
LETHAL
. Follow all instructions
provided. Work involving electric power MUST be performed ONLY by qualified individuals. All required
precautions to prevent contact with live electrical conductors MUST be taken. Failure to comply with these
instructions is an immediate hazard with a likelihood of death or serious personal injury!
3.2.6.1 General.
(a) Codes.
All wiring and wiring methods shall be in strict compliance with NEC and local codes.
(b) Personnel.
All wiring shall be performed by a licensed electrician.
(c) Power Supply Specification.
The Model SC-W assembly uses 120 VAC, 60 Hz, single-phase, 3-wire (HOT,
NEUTRAL, GROUND) power, and draws 14 A.
(d) Power for Accessories.
UNITED
Fire Systems
recommends that power for accessories (such as a condensate
pump) be a separate wiring run from its own circuit breaker, and not be combined with the Model SC-W assembly
power or connected to the Model SC-W assembly terminal strip.
(e) Wire Size.
Refer to
Table 6.
Содержание Nitrogen Pac SC-W
Страница 2: ... THIS SURFACE DELIBERATELY LEFT BLANK ...
Страница 81: ...Page 1 of 6 Model NA 2 Nitrogen Analyzer Hand Held OPERATING MANUAL INSTRUCTIONS FOR USE R218M06 Industrial ...
Страница 102: ...APPENDIX F SC W MANUAL ...
Страница 103: ...APPENDIX F SC W MANUAL ...
Страница 104: ...APPENDIX G SC W MANUAL ...
Страница 111: ... THIS SURFACE DELIBERATELY LEFT BLANK ...