VersaPro Temperature Controller
Page 77
Copyright © 2013, United Process Controls Inc.
All rights to copy, reproduce and transmit are reserved
BLOCK 2
HEX
DEC PARAMETER
DESCRIPTION
READ/WRITE
RANGE = 0 to 999
DEFAULT = 30
Burnoff function available for Redox, Carbon, and
Dewpoint.
34
52
VSTD
VERIFY TEST GAS STANDARD
For oxygen process this is the test standard value
used to verify the probe.
RANGE = 0 to 999
Where the value 999 = 99.9% oxygen
DEFAULT = 30 (3.0%)
For TruCarb this is the FTCS calibration value.
This is the temperature correction factor in
milliohms to compensate the wire resistance
during decarb for the temperature measured
during the decarb process.
READ ONLY
35
53
VTOL
VERIFY TEST TOLERANCE SETTING
This setting establishes the limit as VSTD
VTOL
when comparing to the measured value VGAS
Range = 0 to 999
Where 0005 = 00.5%
DEFAULT = 0005
Verify function available for Oxygen.
READ ONLY
36
54
TAVE
VERIFICATION SAMPLE AVERAGING SETTING
(SECONDS)
RANGE = 0 to 999
DEFAULT = 2
Verify function available for Oxygen.
READ ONLY
37
55
TDEL1
VERIFY DELAY 1 SETTING (SECONDS)
RANGE = 0 to 999
DEFAULT = 30
Verify function available for Oxygen.
READ ONLY
38
56
TDEL2
VERIFY DELAY 2 SETTING (SECONDS)
RANGE = 0 to 999
DEFAULT = 30
Verify function available for Oxygen.
READ ONLY
39
57
TMIN
MINIMUM TEMPERATURE FOR PROBE CARE
TEST
This setting establishes the lowest process
temperature allowed for a probe test or TruCarb
decarburization process to proceed.
RANGE = 500°F to 2000°F (260°C to 1090°C)
DEFAULT = 1400°F (760°C)
NOTE: This value must be checked in the SETUP
menu when the temperature scales have been
changed.
READ ONLY
3A
58
TC_ZERO
TC ZERO CALIBRATION NUMBER
READ/WRITE
3B
59
TC_SPAN
TC SPAN CALIBRATION NUMBER
READ/WRITE
3C
60
MV_ZERO
MV ZERO CALIBRATION NUMBER
READ/WRITE
3D
61
MV_SPAN
MV SPAN CALIBRATION NUMBER
READ/WRITE
3E
62
DAC_OFFSET_1
DAC 1 OFFSET CALIBRATION
READ ONLY