VersaPro Temperature Controller
Page 31
Copyright © 2013, United Process Controls Inc.
All rights to copy, reproduce and transmit are reserved
Pressing the Setup key once at any point in the Setup menu will return the instrument to the normal process
display.
9.4
Dual Key Functions
The VersaPro was four dual key functions as defined below:
RIGHT arrow / Enter
Start probe test sequence
LEFT arrow / Enter
Start Timer
DOWN arrow / Enter
Edit Remaining Timer
Rem / Enter
Monitor Mode
Starting Probe Tests
Pressing the RIGHT arrow / Enter keys simultaneously will start the probe tests if a probe test function has
been selected in the Probe Setup Menu, parameter Probe Test, and the probe temperature is above the
minimum probe temperature parameter in the same menu.
If there is a value other than 0 entered in the Probe Test Interval parameter the probe test will be performed
after the selected interval time has elapsed from the time the test was manually started. If the interval time is
set to 0 then no additional tests will be performed until the next manual start. Starting the test through this dual
key function is the same as if the Start Test parameter in the Probe menu had been changed from NO to YES.
Start Timer
Pressing the LEFT arrow / Enter keys simultaneously will start the timer if the timer has been enabled in the
Control Setup menu, the timer setpoint is greater than zero, and an alarm contact has been assigned a timer
function. Press both keys while the timer is running will stop the timer.
Edit Timer
Pressing the DOWN arrow / Enter keys simultaneously while the timer is running will allow the remaining time
to be changed. The remaining time can be increased or decreased. The change in time takes effect when the
Enter key is pressed and the display returns to the normal remaining time display.
Monitor Mode
Monitor Mode is used by factory personnel only. Return to operate mode by cycling power or sending the
appropriate command word to the instrument.