VersaPro Temperature Controller
Page 28
Copyright © 2013, United Process Controls Inc.
All rights to copy, reproduce and transmit are reserved
Parameter Name
Units or Options
Range
Description
0 or DAC_OFFSET
for PROG
ANALOG 1 RANGE
Span scaling for
selected process
value or percent
output.
0 to 9999 for O2,
LIN, and Temp
HIPO for POUT
4096 or DAC_SPAN
for PROG
This is the maximum value of the
process associated with the
20mA output. The magnitude of
this number is based on the
display resolution.When POUT is
selected this value is fixed to the
HIPO value.
When PROG is selected the
range is fixed at 4096
ANALOG 2 UNIT
LIN A, LINB B,
TENP, POUT, PO1,
PO2 , PROG
Same as Analog 1
ANALOG 2 OFFSET
Offset for selected
process value or
percent output.
Same as Analog 1
ANALOG 2 RANGE
Span scaling for
selected process
value or percent
output.
Same as Analog 1
Table 7 Alarm Menu (ALr)
Parameter Name
Units or Options
Range
Description
ALARM 1 TYPE
OFF
FSHI,
FSLO
dUbd
dbHI
dbLO
HIPO
LOPO
FALt
PROB
tinE
Strt
SOAk
OFF
disables alarm contact.
FSHI - Full Scale HI
, active when
process is above ALARM 1
VALUE.
FSLO - Full Scale LO
, active
when process is below ALARM 1
VALUE.
dUbd – Deviation Band
available for the controller only,
active when process is outside of
symmetrical band around
setpoint.
dbHI – Deviation High
, defines a
process band above the process
setpoint. The alarm is active if
the process moves outside this
band.
dbLO – Deviation Low,
defines
a process band below the
process setpoint. The alarm is
active if the process moves
outside this band.