Parameter Name
Units or Options
Range
Description
BAUD RATE
1200,2400,4800,9600,19.2K
Default is 19.2K
PARITY
None/Even/Odd
Modbus is always None
DELAY
NONE / 10 / 20 / 30
NONE = 0 Delay
10 = 10 ms delay
20 = 20 ms delay
30 = 30 ms delay
Table 9 Info Menu (InFO)
Parameter Name
Units or Options
Range
Description
MILLIVOLT TEMP IN
MILLIVOLTS
-10-100
Displays direct mV of
Temperature input also called
Input A in linear mode.
MILLIVOLT PROB IN
MILLIVOLTS
0-2000
Displays direct mV reading of
probe input as called Input B in
linear mode.
COLD JUNCTION
DEG (F OR C)
0 – 60°C
Displays actual cold junction
temperature
PERCENT OUTPUT
% Output
LOPO to HIPO
Displays actual % output
FIRMWARE REV
Version number
Table 10 Calibration Menu
Parameter Name
Units or Options
Range
Description
CAL INPUT
NO / YES
Default to NO, must be changed
to YES to enter input calibration
routine.
TC ZERO
(CAL IN)
Changes calibration value for
thermocouple zero
TC SPAN
(CAL IN)
Changes calibration value for
thermocouple span
PROBE mV ZERO
(CAL IN)
Changes calibration value for
millivolt zero
PROBE mV SPAN
(CAL IN)
Changes calibration value for
millivolt span
CJ OFFSET
(CAL IN)
0 – 60° C
0 – 140° F
Sets the cold junction offset
depending on the temperature
range selected
CAL OUTPUT
NO / YES
Default to NO, must be changed
to YES to enter output calibration
routine.
OUTPUT 1 MIN
(CAL OUTPUT)
Sets signal level for the minimum
mA output.
OUTPUT 1 SPAN
(CAL OUTPUT)
Sets signal level for the maximum
mA output.
OUTPUT 2 MIN
(CAL OUTPUT)
Sets signal level for the minimum
mA output.
OUTPUT 2 SPAN
(CAL OUTPUT
Sets signal level for the
maximum mA output.