VersaPro Temperature Controller
Page 70
Copyright © 2013, United Process Controls Inc.
All rights to copy, reproduce and transmit are reserved
BLOCK 0
HEX
DEC
PARAMETER
DESCRIPTION
READ/WRITE
BIT 4 ACTION CONTROL
0 = DIRECT
1 = REVERSE
BIT 5 NO LATCH = 0 LATCHED = 1
BIT 6 – 15 SPARE
0A
10
PB
Proportional Band – Based on display units
Range = 1 to 9999
Default = 20
READ ONLY
0B
11
RESET
Reset – Based on seconds
Range = OFF to 9999
Where 0020 is assumed to be 00.20 seconds
Default = OFF (reset value = 0)
READ ONLY
0C
12
RATE
Rate – Based on seconds
Range = OFF to 9999
Where 0020 is assumed to be 00.20 seconds
Default = OFF (rate value = 0)
READ ONLY
0D
13
CYCTIM
Cycle Time – Based on seconds
Range = 0.2 to 9999
Where 0002 is assumed to be 0002 seconds
Default = 30
READ ONLY
0E
14
RSTC
TruCarb Sensor real time resistance not corrected
for resistance due to temperature. The value is an
integer with an implied milliohm resolution.
READ ONLY
0F
15
HIPO
Control Output High Limit
Range = -100 to 100 where HIPO is always
greater than LOPO.
Default = 100
READ ONLY
10
16
LOPO
Control Output Low Limit
Range = -100 to 100 where LOPO is always less
than HIPO.
Default = 0
READ ONLY
11
17
CONMD
Control Type setting
BITS 0 – 3= CONTROL PARAMETER
0000 = SPARE
0001 = Temperature
0010 = Millivolt INPUT B
0011 = Carbon
0100 = Dewpoint
0101 = Oxygen
0110 = Redox
0111 = Millivolt INPUT A
1000 = GC Carbon
BIT 4 = NORMAL (0) FREEZE CONTROL
OUTPUT (1)
BITS 5 – 7 = MODE
000 = TIME PROPORTIONING
READ ONLY