Parameter Name
Units or Options
Range
Description
source.
IN A SLOPE
Only in Linear mode
-999 – 999
-99.9 – 99.9
-9.99 – 9.99
-.999 - .999
Linear slope to scale Input A to
Engineering Units when INPUT A
is selected as the process
source.
This is the slope number in the
linear calculation where: EU =
SLOPE(mV) + OFFSET
See key
TEMP SCALE
F OR C
Sets temperature scale.
TC FILTER
SECONDS
0 – 450
Temperature filter setting in
seconds. Filters the temperature
value with a moving average time
window.
IN B OFFSET
Works only in mV
Mode
-999 – 9999
Linear offset to scale Input B to
Engineering Units when INPUT B
is selected at the process source.
This is the offset in used in the
SLOPE(mV) + OFFSET equation.
IN B SLOPE
Works only in mV
Mode
-999 – 999
-99.9 – 99.9
-9.99 – 9.99
-.999 - .999
Linear slope to scale Input B to
Engineering Units when INPUT B
is selected as the process
source.
This is the slope number in the
linear calculation where: EU =
SLOPE(mV) + OFFSET
MV FILTER
SECONDS
0 – 450
Millivolt filter setting in seconds.
Filters the millivolt reading with a
moving average time window.
Table 5 Calculation Menu (CALC)
Parameter Name
Units or Options
Range
Description
DISPLAY DECML PT
Decimal point
0-4
Sets decimal pt., available for
Input A and Input B.
Table 6 Analog Output Menu (AOUt)
Parameter Name
Units or Options
Range
Description
ANALOG 1 UNIT
LIN A, LINB B,
TENP, POUT, PO1,
PO2 , PROG
4 to 20mA output.
ANALOG 1 OFFSET
Offset for selected
process value or
percent output.
-30.0 to 300.0 for O2
and LIN
-300 to 3000 for
temperature
LOPO for POUT
This is the minimum value of the
process associated with the 4mA
output. The magnitude of this
number is based on the display
resolution.
In POUT mode the offset is fixed
to the LOPO value.
When PROG is selected the
offset is fixed at 0