VersaPro Temperature Controller
Page 71
Copyright © 2013, United Process Controls Inc.
All rights to copy, reproduce and transmit are reserved
BLOCK 0
HEX
DEC
PARAMETER
DESCRIPTION
READ/WRITE
001 = TIME PROP W/ COMPLEMENT
010 = TIME PROP, DUAL
011 = SPARE
100 = ON/OFF
101 = ON/OFF W/ COMPLEMENT
110 = ON/OFF, DUAL
111 = VALVE POSITIONING W/ FEEDBACK
BIT 8 = DIRECT (0) OR REVERSE (1)
ACTING
BIT 9 = MANUAL (0) OR AUTO (1)
BIT 10 = SETPT LOCAL (0) OR SETPT REMOTE
(1)
BIT 11 = MONITOR (0), CONTROLLER (1)
BITS 12 = SENSOR BREAK OUTPUT 0 (0),
OUTPUT HOLD (1)
BITS 13 – 15 NOT USED
12
18
CONFIG0
Input Configuration
BITS 0-3 TC Input TYPE
0000 = B (DEFAULT)
0001 = E
0010 = J
0011 = K
0100 = N
0101 = R
0110 = S
0111 = T
1000 = SPARE
1001 = SPARE
1010 = SPARE
1011 = SPARE
1100 = SPARE
1101 = SPARE
1110 = SPARE
1111 = SPARE
BIT 4 = SPARE
BIT 5 0 = NO CJ APPLIED, 1 = CJ APPLIED
BIT 6 0 = °F, 1 = °C
BIT 7 0 = 60HZ FILTER
BIT 8 – 11 Millivolt Input TYPE
0000 = LINEAR (DEFAULT)
All other bit combinations are spare
BITS 12 – 15 are spare
READ ONLY
13
19
CTRLOUT
Control Output, unsigned integer
Actual control output where:
READ ONLY