Important notes:
Mounting surface blank metal, not varnished (surface EMC contact)
Check device for mechanical damage. Mount only perfect devices.
Cut all power prior to assembly.
Insert shortening plug and attach warning signs at installations
already electrically connected.
Assembly permitted only by competent professionals.
Vertical mounting position.
Note power reduction if mounted horizontally.
Ensure adäquatem ventilation clearance. (at least 100mm).
Use dimension diagram or drill template to trace fastening holes of
device.
Do not mark off from device.
Drill mounting holes (M4) in mounting base.
Screw in screws up to 4mm.
Insert device and tighten screws.
Mount filter and choke near to device.
Surface-contact line shields to mounting surface.
Keep unshielded cable ends as short as possible.
Brake resistors can become very hot. (200°C).
Mount resistors so that neither injuries (burns) nor damage caused by their heat can occur.
Use vibration-proof bolted joints.
Ensure adequate control cabinet ventilation. Use air conditioners for excessive room
temperatures (>30°C).
Caution: Operation with devices covered in dew is not permissible!