18
2
INSTALLATION AND CONNECTION
18
INST
ALLATION AND CONNECT
ION
Chapter
2
■
How to assemble the connector
1.
Set the connector and screws (two) into the grooves of the case (one side).
2.
Cover with the other case, and fit the cases.
3.
Tighten the M2
×
8 pan-head machine screws (two).
Tighten the M2
×
10 pan-head machine screws (two).
Be aware that washers should be set to the M2
×
10 pan-head machine screws
(two).
Input signals
- Load Digital Zero
It should normally be wired. Perform Digital Zero
by unloading the load sensor before measurement
to simply adjust the deviation of the zero point of
the load by temperature drift, etc. The load is
zeroed by turning the signal from OFF to ON. As long as the signal is ON, the Load OK output
is kept OFF.
* Digital zero value is cleared when the power supply is turned on.If you want to
maintain digital zero value, Please do zero calibration instead.
- DPM Positioning
It should be wired according to application. Use it
for adjusting the zero point of displacement just
before measurement start.
It is not used if the X-axis of the waveform
represents time or the zero point of displacement does not need to be adjusted. By turning the
signal from OFF to ON, displacement is brought to the DPM Positioning set value, and the
internal counter of the pulse input is cleared. As long as the signal is ON, the DPM OK output is
kept OFF.
- Start
It should normally be wired. Use it for starting
measurement. By turning the signal from OFF to
ON when the Start signal input is waited for, a
“Wait Off” state is brought about, and the Hold
Connector
Pan-head machine screw
M2
×
8 (short) (two)
Nut M2 (four)
Pan-head machine screw
M2
×
10 (long) (two)
Washer (two)
Case (two)
Screw (two)
Load Digital
OFF
ON
Keep ON for
1.5ms or more.
Zero input
DPM
OFF
ON
Keep ON for
1.5ms or more.
Positioning
input
Start input
OFF
ON
Keep ON for
1.5ms or more.
Содержание DeviceNet F381A
Страница 1: ...15APR2013REV 3 10 DYNAMIC FORCE PROCESSOR F381A OPERATION MANUAL ...
Страница 9: ...Contents VIII Contents VIII M E M O ...
Страница 34: ...25 2 INSTALLATION AND CONNECTION 25 INSTALLATION AND CONNECTION Chapter 2 M E M O ...
Страница 147: ...138 8 SPECIFICATIONS 138 SPECIFICATIONS Chapter 8 8 2 Outside dimensions Unit mm ...
Страница 164: ......