12.4
Output Voltage
- The output voltage is factory set to its nominal value to an accuracy of
±1%. The voltage can be adjusted to any value within the range given in the table below
using the PMBus interface.
MODEL
ADJUSTMENT
RANGE
TBSR3000, RBSR12/100
7.5-15V
TBSR5000, RBSR24/54, RBSR24/60
15-30V
TBSR7000, RBSR28/28, RBSR48/37
30-60V
12.5
Output Power & Current
- The following table shows the maximum output power and
current ratings for the various models:
MAX.
POWER
OUTPUT
VOLTAGE
OUTPUT
CURRENT
INPUT
VOLTAGE
INPUT
CURRENT
MODEL
NO.
2000W
1500W
54.4VDC
37.0A
28.0A
180-264VAC
85-132VAC
10A
14A
RBSR48/37
1500W
54.4VDC
28.0A
85-264VAC
14A/7.5A
RBSR48/28
2000W
1500W
48.0VDC
42.0A
31.0A
180-264VAC
85-132VAC
10A
14A
TBSR7000
1632W
1469W
27.2VDC
60.0A
54.0A
180-264VAC
85-132VAC
8.2A
13.5A
RBSR24/60
1469W
27.2VDC
54.0A
85-264VAC
13.5A/7.6A
RBSR24/54
1440W
24.0VDC
60.0A
85-264VAC
13.3A/7.3A
TBSR5000
1360W
13.6VDC
100.0A
85-264VAC
12.5A/7A
RBSR12/100
1200W
12.0VDC
100.0A
85-264VAC
11.0A/6.5A
TBSR3000
Models showing two output power levels with dual AC input ranges automatically limit the
output current according to the actual input voltage present.
When the output voltage is adjusted below the nominal voltage shown in the table the
maximum current indicated will apply. Conversely, when the output voltage is adjusted
above the nominal voltage shown the maximum power indicated will apply.
The maximum output power may be drawn up to +50°C air inlet temperature. Above +50°C
the total output power must be derated by 2.5%/°C, up to an absolute maximum air inlet
temperature of +70°C. Note that dependent on actual airflow through the unit output power
may be further limited or a temperature alarm indicated at lower temperatures.
The two standby outputs of +5V @ 1.8A and +12V @ 0.8A are limited to a combined output
power of 9.6W.