Page 22
BLUESTREAK SERIES
INSTALLATION & OPERATING MANUAL
P O W E R I N G T E C H N O L O G Y
Document Number: BLUESTREAK-MAN Rev. 6
bluestreak-man-rev6-0719.indd
The DC output is supplied on two pairs of internally connected bus bars with four 1/4-20
threaded bolts for each bar spaced 0.625” apart. Each pair has a maximum current capacity
of 200A. Various pre-made cables suitable for connection to these bus bars are detailed on
the BLUEstreak datasheet and must be ordered separetely if required.
Note that for installations where greater than 200A output current is required it is necessary
to use both pairs of bus bars for connection to the load.
J1 is a 25-way D-type socket providing the alarm, control and supervisory signals. J2
is an RJ25 socket providing connections for the PMBus. J3 is a spring clamp terminal
block providing two connections each for +Ve Sense, -Ve Sense and Current Share. This
facilitates easy daisy-chaining of these connections where two or more power shelves are
being connected in parallel. These terminals accept wire sizes in the range #28 to #20 AWG.
The following tables and figures show the pinout for these connectors. Details of each pin
function can be found in section 9.2.
SIGNAL CONNECTOR - J1
PIN FUNCTION
PIN FUNCTION
J1 - 25-Way D-Type
1
13
14
25
1
Control
14
#ACOK - 1
2
12V Standby
2, 3
15
#DCOK - 1
3
#TEMPOK - 1
16
#ACOK - 2
4
#TEMPOK - 2
17
#DCOK - 2
5
#TEMPOK - 3
18
#ACOK - 3
6
#TEMPOK - 4
19
#DCOK - 3
7
Remote Adjust
4
- 4
20
#ACOK - 4
8
5V Standby
1, 3
21
#DCOK - 4
9
#MODULE PRESENT - 1
22
Sense –Ve
10
#MODULE PRESENT - 2
23
Standby Return
11
#MODULE PRESENT - 3
24
Remote Adjust
4
- 1
12
Remote Adjust
4
- 2
25
Remote Adjust
4
- 3
13
#MODULE PRESENT - 4
NOTES: 1. Current rating of +5V standby is 1.8A per module.
2. Current rating of +12V standby is 0.8A per module.
3. Total standby consumption limited to 9.6W per module.
4. Referenced to -Ve Sense.
SIGNAL CONNECTOR - J2
PIN FUNCTION
PIN FUNCTION
1
#SMBALERT
4
5V Standby
J2 - RJ45
8
1
2
SDA
5
SCL
3
Standby Return
6
Control