CODE NAME
SHORT DESCRIPTION
CODE NAME
SHORT DESCRIPTION
01h
OPERATION
Used for on/off and margining
78h
STATUS_BYTE
Reads the status byte
02h
ON_OFF_CONFIG
Used to configure the function of
OPERATION
79h
STATUS_WORD
Reads the status word
03h
CLEAR_FAULTS
Clears status bytes and
SMBALERT signal
7Ah
STATUS_VOUT
Reads the VOUT status register
12h
RESTORE_DEFAULT_ALL
Restores all user parameters
from default store
7Bh
STATUS_IOUT
Reads the IOUT status register
15h
STORE_USER_ALL
Stores all user parameters in the
user store
7Ch
STATUS_INPUT
Reads the INPUT status register
16h
RESTORE_USER_ALL
Restores all user parameters
from user store
7Dh
STATUS_TEMPERATURE
Reads the TEMPERATURE
status register
20h
VOUT_MODE
Reads the data format for VOUT
related commands
7Eh
STATUS_CML
Reads the CML status register
21h
VOUT_COMMAND
Sets the output voltage
81h
STATUS_FANS_1_2
Reads the FAN status register
22h
VOUT_TRIM
Trims the output voltage
88h
READ_VIN
Reads the VIN voltage value
24h
VOUT_MAX
Sets the voltage above which an
alert will be issued
8Ah
READ_VCAP
Reads the VCAP voltage value
25h
VOUT_MARGIN_HIGH
Sets the output voltage when
high margin is set
8Bh
READ_VOUT
Reads the output voltage value
26h
VOUT_MARGIN_LOW
Sets the output voltage when
low margin is set
8Ch
READ_IOUT
Reads the output current value
27h
VOUT_TRANSITION_RATE
Sets the rate of change of output
voltage
8Dh
READ_TEMPERATURE_1
Reads the internal temperature
value
42h
VOUT_OV_WARN_LIMIT
Sets the output over voltage
warning limit
90h
READ_FAN_SPEED_1
Reads the speed of fan 1
43h
VOUT_UV_WARN_LIMIT
Sets the output under voltage
warning limit
91h
READ_FAN_SPEED_2
Reads the speed of fan 2
44h
VOUT_UV_FAULT_LIMIT
Sets the output under voltage
fault limit
98h
PMBUS_REVISION
Reads the revision of the PMBus
implementation
45h
VOUT_UV_FAULT_RESPONSE
Sets the output under voltage
fault response
99h
MFR_ID
Reads the manufacturer ID
46h
IOUT_OC_FAULT_LIMIT
Sets the output over current
fault limit
9Ah
MFR_MODEL
Reads the power supply model
number
47h
IOUT_OC_FAULT_RESPONSE
Sets the output over current fault
response
9Bh
MFR_REVISION
Reads the power supply
hardware revision
4Ah
IOUT_OC_WARN_LIMIT
Sets the output over current
warning limit
9Ch
MFR_LOCATION
Reads the power supply
manufacturer location
4Fh
OT_FAULT_LIMIT
Sets the over temperature fault
limit
9Dh
MFR_DATE
Reads the power supply
manufacture date
50h
OT_FAULT_RESPONSE
Sets the over temperature fault
response
9Eh
MFR_SERIAL
Reads the power supply serial
number
51h
OT_WARN_LIMIT
Sets the over temperature
warning limit
D0h
OVP_SETTING
Sets the OVP voltage level
52h
UT_WARN_LIMIT
Sets the under temperature
warning limit
D1h
READ_ISHARE
Reads the ISHARE current level
53h
UT_FAULT_LIMIT
Sets the under temperature
fault limit
D2h
READ_VOUT_BUTTON_ADJ
Reads the voltage adjustment
offset of the buttons
54h
UT_FAULT_RESPONSE
Sets the under temperature fault
response
D3h
MINIMUM_FAN_SPEED
Sets the minimum fan speed
5Eh
POWER_GOOD_ON
Sets the output power good turn
on voltage level
D4h
MISC_CONFIG
Enables front panel buttons,
signal polarity,
5Fh
POWER_GOOD_OFF
Sets the output power good turn
off voltage level
D5h
SOFTWARE_REVISION
Reads the software revision
60h
TON_DELAY
Sets the time before the output
voltage comes up
D6h
MODEL
Reads the basic hardware model
(12,24,48)
61h
TON_RISE
Sets the output voltage rise time.
D7h
PART_NUMBER
Reads the module part number
(001-xxxx-xxxx)
64h
TOFF_DELAY
Sets the delay time before the
output goes off
Figure 15 - PMBus Command Summary