17.0  SHELF INSTALLATION

17.1 Mounting 

- BLUEstreak Series 19-inch rack-mount power shelves are provided with 

universal rack- brackets that allows them to be mounted into a 1U high space in both 19-

inch and 23-inch racks.  The brackets can be located at various positions in the side of the 

shelf to allow for offset mounting in the rack.

 

To minimise obstruction to ventilation UNIPOWER advises that any equipment mounted 

directly above the BLUEstreak power shelf should be shorter in overall depth.

17.2 

Input Power Connections 

- Depending on the exact model AC input power connections 

are made to the IEC60320-C20 or Terminal Blocks mounted at the rear of the power shelf.  
Each module position has its own input connector or terminals.  For models incorporating 

IEC60320-C20 connectors UNIPOWER can supply various line cords; see the current 

datasheet for details.  For models with Terminal Block connections a 3-wire connection 

is required for each module position that is to be used.  The minimum suitable cable size 

for these connections is 14AWG or equivalent.  It is recommended that each input feed is 

protected by its own circuit breaker.  When using the version with Terminal Blocks the 

supplied safety covers should be fitted.  The terminal block connections are #8-32 threaded 

screws with a 0.437” spacing, see figure 12 below.

 

J1

J2 J3 SW1

OUTPUT A

AC4/AC3

or

DC4/DC3

+V

+V

- V

- V

200A Max.

200A Max.

Frame

Ground

AC2/AC1

or

DC2/DC1

OUTPUT B

0.437 (11.10)

0.625 (15.88)

1/4-20

8-32

8-32

0.5” length

Figure 12 - AC Screw Terminal Detail

17.5 

DC Output Connections

 - DC output connections are provided at the rear of the power 

shelf on two pairs of bus bars.  Each pair is rated to carry a maximum of 200A.  On single 

bus power shelves the bus bars are connected internally thus allowing a total output current 

of 400A maximum when both bars are used.  On dual bus power shelves the two pairs of bus 

bars are isolated from each other and thus allow side A to have different voltage modules 

installed to side B.  In all cases the output polarity can be configured either positive or negative 

as desired.  Dual bus shelves will allow for a true A+B supply to equipment requiring such a 

facility.  The  four 1/4-20 threaded bolts on each bar are spaced 0.625” apart. UNIPOWER 

can supply various pre-made DC load cables; see the current datasheet for available options.  

Users wishing to fabricate their own DC cables should note that such cables should be rated 
to handle at least 300A.

8-32 threaded screws

Содержание Bluestrak Series

Страница 1: ...RECTIFIERS Document Number BLUESTREAK MAN Rev 6 UNIPOWER LLC 65 Industrial Park Rd Dunlap TN 37327 Phone 1 954 346 2442 Toll Free 1 800 440 3504 Web site www unipowerco com 2019 UNIPOWER LLC All Right...

Страница 2: ...ND INSPECTION 6 7 0 MODULE SPECIFICATIONS 7 8 0 FRONT PANEL DESCRIPTION 7 9 0 DESCRIPTION OF OPERATION 9 10 0 MECHANICAL SPECIFICATIONS 14 11 0 SAFETY AND INDUSTRY STANDARDS 15 13 0 PARALLEL OPERATION...

Страница 3: ...Rear View showing connection details 15 Figure 7 Mating Interface Board 16 Figure 8 Connection Diagram for Parallel Operation 19 Figure 9a Model TBSR1U4A with IEC Connectors 21 Figure 9b Model TBSR1U...

Страница 4: ...to 24 watts per cubic inch The modules have automatic load sharing and active output ORing circuit so they can be hot swapped while the system is operating Using PMBus compliant serial communications...

Страница 5: ...0A 54 0A 180 264VAC 85 132VAC 8 2A 13 5A RBSR24 60 1469W 27 2VDC 54 0A 85 264VAC 13 5A 7 6A RBSR24 54 1440W 24 0VDC 60 0A 85 264VAC 13 3A 7 3A TBSR5000 1360W 13 6VDC 100 0A 85 264VAC 12 5A 7A RBSR12...

Страница 6: ...aterial and workmanship This warranty does not extend to products which have been opened altered or repaired by persons other than persons authorized by the manufacturer or to products which become de...

Страница 7: ...6 75 Load to 92 0 40 Load to 91 0 SAFETY CERTIFICATIONS UL60950 1 2nd Ed CSA22 2 No 60950 1 2nd Ed EN60950 1 2nd Ed STATUS INDICATORS STATUS Green LED FAULT Red LED ALARM SIGNALS open drain TTL compa...

Страница 8: ...r disable the buttons Note that it may be necessary to adjust the settings of DCOK and OVP using the PMBus in order not to encounter these when adjusting with the push buttons over a wide voltage rang...

Страница 9: ...he power supply and sense wiring Sense Ve and Sense Ve are internally connected to the module output power terminals using 10 Ohm resistors so that if the senses are not connected the output will stil...

Страница 10: ...ages of up to 30V and will sink current up to 30mA The return path for this signal is standby return The ACOK signal is also available within the status bytes of the PMBus The ACOK signal will give ty...

Страница 11: ...output off This function can be changed using PMBus so that either a high signal will turn the main output off or the pin is ignored altogether This behaviour can allow a system to be setup so that t...

Страница 12: ...gh Timing given is for 2000Watt load on 48V model TON_RISE 50ms Time for DC output to rise to final regulated value This is reprogrammable with PMBus T5VSB_RISE 3ms 5ms 10ms Time for 5VSB to rise to f...

Страница 13: ...REAK MAN Rev 6 bluestreak man rev6 0719 indd ACV Input DC Main Output ACOK DCOK 5V SB 12V SB CONTROL AC ON AC ON TON RISE TVOUT HOLDUP TACOK FALL TACOK ON TACOK RISE TACOK OFF TDCOK FALL TDCOK ON TDCO...

Страница 14: ...AN Rev 6 bluestreak man rev6 0719 indd 10 0 MECHANICAL SPECIFICATIONS The mechanical dimensions of the BLUEstreak module are shown Note that BLUEstreak modules are designed for hot swap applications o...

Страница 15: ...rges line to ground EN61000 4 5 level 4 criteria A ESD EN61000 4 2 level 4 criteria A Radiated EN61000 4 3 criteria A 10V m Dips Interruptions Variations EN61000 4 11 criteria B C 12 0 OPERATING INFOR...

Страница 16: ...B2 Control D2 Current Share 4 B3 GA2 D3 GA0 B4 Standby Return D4 12V Standby 2 3 B5 TEMPOK D5 ACOK B6 SDA D6 ENABLE Notes 1 Current rating of 5V standby is 1 8A 2 Current rating of 12V standby is 0 8...

Страница 17: ...9W 27 2VDC 60 0A 54 0A 180 264VAC 85 132VAC 8 2A 13 5A RBSR24 60 1469W 27 2VDC 54 0A 85 264VAC 13 5A 7 6A RBSR24 54 1440W 24 0VDC 60 0A 85 264VAC 13 3A 7 3A TBSR5000 1360W 13 6VDC 100 0A 85 264VAC 12...

Страница 18: ...ion occurs is programmable down to the minimum default setting 12 8 Remote Sensing Remote sensing connections are made to pins B1 and C1 on the connector Remote sensing is not available on the 5V or 1...

Страница 19: ...into the module 1 1 redundancy with quick replacement of a failed unit results in virtually infinite MTBF 2 1 or 3 1 redundancy works the same way except that the full load is carried by two out of th...

Страница 20: ...power shelves or similar OEM housing Fixing in place is achieved by means of a latching mechanism that is also used to push the module home into the mating connector For OEMs wishing to install the BL...

Страница 21: ...Block Input AC or DC 400A TBSR1U4B 8000W Dual Output Bus IEC60320 C20 Input AC only 200A 200A TBSR1U4C 8000W Dual Output Bus Terminal Block Input AC or DC 200A 200A TBSR1U4D Blanking kit for unused po...

Страница 22: ...e and Current Share This facilitates easy daisy chaining of these connections where two or more power shelves are being connected in parallel These terminals accept wire sizes in the range 28 to 20AWG...

Страница 23: ...0x3A 0x3C 0x3E ON OFF ON 0x30 0x32 0x34 0x36 ON ON OFF 0x28 0x2A 0x2C 0x2E ON ON ON 0x20 0x22 0x24 0x26 Note Module numbers 1 to 4 are left to right when viewed from the front fan grille end 15 3 Dual...

Страница 24: ...respectively J2Aand J2B are RJ25 sockets providing PMBus for modules installed in the A and B side respectively The following tables and figures show the pinout for these connectors Details of each pi...

Страница 25: ...CONNECTORS J2A J2B J2A J2B PIN FUNCTION PIN FUNCTION 1 SMBALERT A 1 SMBALERT B J2A J2B RJ45 8 1 2 SDA A 2 SDA B 3 Standby Return A 3 Standby Return B 4 5V Standby 1 3 A 4 5V Standby 1 3 B 5 SCL A 5 S...

Страница 26: ...O G Y Document Number BLUESTREAK MAN Rev 6 bluestreak man rev6 0719 indd 16 0 MECHANICAL DIMENSIONS Figure 11 below shows outline dimensions for the BLUEstreak Series Power Shelves 18 98 482 1 1 72 43...

Страница 27: ...tions is 14AWG or equivalent It is recommended that each input feed is protected by its own circuit breaker When using the version with Terminal Blocks the supplied safety covers should be fitted The...

Страница 28: ...rs together and one for connecting the two negative bus bars together The two link bars are identical and interchangeable V V V V V V 3 shelf kit part number 775 1509 0030 Contains two long link bars...

Страница 29: ...in Parallel To ensure proper power sharing between parallel connected power shelves it is important to make sure that current share and Ve Sense are connected between each shelf See sections 15 2 and...

Страница 30: ...terface board or a power shelf the Enable pin is automatically connected to Ve Sense The units are then controlled by the Control inputs 19 5 Checking Front Panel LEDs With the BLUEstreak module on th...

Страница 31: ...emote sense leads to the load being careful to connect the correct polarity Note the comments in section 9 2 1 regarding circuit breakers or fuses in the output power feed 19 11 Turn on or plug in the...

Страница 32: ...o use this program a PC to I C Adaptor is required and UNIPOWER recommends and can supply the I2C2PC Adaptor detailed at www i2cchip com pdfs i2c2pc pdf This adaptor provides both RS232 and USB connec...

Страница 33: ...1 4 Set the link J3 on the I2C 2 PC Adaptor under the 9 way serial connector towards the USB connector to select the USB connector 20 2 How to use the program If using the program with a BLUEstreak s...

Страница 34: ...s the output under voltage warning limit 91h READ_FAN_SPEED_2 Reads the speed of fan 2 44h VOUT_UV_FAULT_LIMIT Sets the output under voltage fault limit 98h PMBUS_REVISION Reads the revision of the PM...

Страница 35: ...g condition Fans below expected speed Temperature high or low Output current close to maximum Output on but DCOK is FALSE AC supply outside of normal range OFF DC Output is on No warning or alarm cond...

Отзывы: