Page 24
BLUESTREAK SERIES
INSTALLATION & OPERATING MANUAL
P O W E R I N G T E C H N O L O G Y
Document Number: BLUESTREAK-MAN Rev. 6
bluestreak-man-rev6-0719.indd
The DC output is supplied on two pairs of bus bars with four 1/4-20 threaded bolts for each
bar spaced 0.625” apart. One pair for the A Bus one pair for the B Bus. The A Bus is fed
from modules installed in positions A1 and A2 while the B Bus is fed from modules installed
in positions B1 and B2. Each pair has a maximum current capacity of 200A. The two
buses are fully isolated from each other and may be configured for different combinations
of output voltage and/or polarity.
J1A and J1B are 15-way D-type sockets providing the alarm, control and supervisory
signals for modules installed in the A and B side respectively. J2A and J2B are RJ25 sockets
providing PMBus for modules installed in the A and B side respectively. The following
tables and figures show the pinout for these connectors. Details of each pin function can
be found in section 9.2.
SIGNAL CONNECTORS - J1A & J1B
J1A
J1B
PIN
FUNCTION
PIN
FUNCTION
1
Control - A
1
Control - B
J1A & J1B – 15-Way D-Type
1
8
9
15
2
12V Standby
2, 3
- A
2
12V Standby
2, 3
- B
3
#TEMPOK - 2
3
#TEMPOK - 4
4
#TEMPOK - 1
4
#TEMPOK - 3
5
5V Standby
1. 3
- A
5
5V Standby
1. 3
- B
6
Remote Adjust
4
- 2
6
Remote Adjust
4
- 2
7
Remote Adjust
4
- 1
7
Remote Adjust
4
- 1
8
#ACOK - 2
8
#ACOK - 4
9
#DCOK - 2
9
#DCOK - 4
10
#ACOK - 1
10
#ACOK - 3
11
#DCOK - 1
11
#DCOK - 3
12
Sense -Ve - A
12
Sense -Ve - B
13
Standby Return - A
13
Standby Return - B
14
Sense +Ve
4
- A
14
Sense +Ve
4
- B
15
Current Share
4
- A
15
Current Share
4
- B
NOTES: 1. Current rating of +5V standby is 1.8A per module.
2. Current rating of +12V standby is 0.8A per module.
3. Total standby consumption limited to 9.6W per module.
4. Referenced to -Ve Sense.