PART III: OPERATION

47

   

Oil pressure switch adjustment

Follow the below instruction, according to the pressure switch installed.

               

Minimum oil pressure switch (when provided)

The minimum oil pressure switch on the inlet line,  checks that the pressure does not drop below a default value. The pressure switch
must be set, say, at 10% under the pressure at the nozzle. 

                       

Maximum oil pressure switch

The oil pressure switch on the return line,  checks that the pressure does not exceed a default value.  This value must not be higher
than the maximum acceptable pressure on the return line (this value is reported on the specification table).  A pressure change on the
return line could affect the combustion parameters:  for this reason, the pressure switch must be set, say, at 20% over the pressure
recorded during the combustion adjustment. The factory setting is 4 bar.
It is recommended to verify that the combustion parameters are within the range of acceptable values even  against a pressure varia-
tion that gets close to the limit of the pressure switch.
This check should be carried out along the whole range of the burner output.
In case of inacceptable values, reduce from 20% to 15% the overpressure; later on, repeat the adjustments described above.

Pressure governor on return line

Pressure governor works between two different pressure values. The minimum pressure value is set by the minimum output setting
pressure screw under the plug 1; The maximum pressure value is set by the plunger stroke “V” and the modulation is obtained with the
movement of the piston in-out. The valve also control the flow in the following way: the higher pressure in the valve has, as consequen-
ces, the less flow through it and also the lower pressure in the valve is, the higher flow through it. On the other side in the nozzle return
line the higher pressure has like consequence the more oil pulverized in the nozzle

                   

ATTENTION: Regulator’s capacity with minimum output setting pressure depends on adjustment of the conic pin.
Avoid a piston stroke higher than 10mm. In this peculiar case with a high value of minimum output setting pres-
sure  can cause the block of the piston - conic pin and break the pin.

HEX6

Trafag Picostat 9B4..

PresiónPressure
Return

Legend

P = Return pressure from spill-back nozzle

R = Return to tank

V = Plunger

1 = Minimum output setting pressure

2 = Modulation: 8-9 stroke

P

R

P

R

1

2

V

Содержание HR2050

Страница 1: ...M039409CC 0 0 01 2023 BURNERS BRUCIATORI BRULERS BRENNER QUEMADORES MANUAL OF INSTALLATION USE MAINTENANCE LMV5x Microprocessor controlled Gas light oil burners HR2050 HR2060 HR2080...

Страница 2: ...non original components whether spare parts kits accessories and optionals Force majeure Furthermore the manufacturer declines all responsibility for non compliance with this manual Personnel training...

Страница 3: ...rner shut down reser the control box by means of the RESET pushbutton If a second shut down takes place call the Tech nical Service without trying to RESET further The unit shall be operated and servi...

Страница 4: ...the ones stated Do not use the burner in potentially explosive environments Do not remove or by pass any machine safety devices Do not remove any protection devices or open the burner or any other com...

Страница 5: ...wo pressure regulators one for the high and one for low pressure in double stage systems with one nozzle The adjustable combustion head can improve the burner performance The combustion head determine...

Страница 6: ...R2080 Output min max kW 2500 15200 2500 16000 2500 19000 Fuel MG Natural gas Light oil Category see next paragraph Gas rate min max min max Stm3 h 265 1608 265 1693 265 2011 Pressure mbar see Note 2 L...

Страница 7: ...6 15 595 132 768 1898 683 2431 1604 827 845 730 949 M16 948 670 239 215 827 1477 310 1314 365 HR2050 100 741 1748 866 15 595 145 768 1898 683 2447 1620 827 845 730 949 M16 948 670 239 215 874 1477 350...

Страница 8: ...75 850 950 M16 1117 790 1066 239 215 827 1336 310 1375 HR2060 100 2377 741 831 868 7 645 321 920 145 885 1877 728 2329 1479 850 775 850 950 M16 1117 790 1113 239 215 874 1336 350 1375 HR2060 125 2377...

Страница 9: ...00 EK 790 395 395 790 395 395 P750 1117 16 M 850 395 395 850 395 395 395 395 30 30 30 395 395 30 700 2178 1375 900 215 741 15 970 550 1892 2442 775 125 239 731 353 1196 1326 638 861 1759 425 950 742 7...

Страница 10: ...PART I SPECIFICATIONS 10 Support frame for burner size 2080 968 1255 1690 1150 1028 164 1370 50 1773 1200 684...

Страница 11: ...Pressure switch 16 One way valve 18 Flexible hose 19 Manual valve 20 Pressure gauge MAIN GAS TRAIN 40 Manual valve 41 Bellows unit 42 Filter 43 Pressure switch PGMIN 44 Safety valve with built in gas...

Страница 12: ...p and pressure governor 4 Electrical motor 6 Solenoid valve 10 Oil distributor 12 Pressure gauge 13 Pressure governor 14 Actuator 15 Pressure switch 16 One way valve 18 Flexible hose 19 Manual valve 2...

Страница 13: ...ilable gas pres sure value upstream the burner s gas valve Then subtract the backpressure The result is called pgas Draw a vertical line matching the furnace input value 600kW in the example quoted on...

Страница 14: ...is diagram the maximum output point is usually reached by adjsuting the combustion head to its MAX position see paragraph Adjusting the combustion head the minimum output point is reached setting the...

Страница 15: ...ESSURE mbar HR2080 Stm3 h Caution the gas rate value is quoted on the x axis the related network pressure is quoted on the y axis pressure value in the combustion chamber is not included To know the m...

Страница 16: ...ssure in the combustion head insert the pressure gauge probes one into the combustion chamber s pres sure outlet to get the pressure in the combustion chamber and the other one into the butterfly valv...

Страница 17: ...ssure burner head vs natural gas flow rate Curves are referred to pressure 0 mbar in the combustion chamber Gas pressure in combustion head HR2050 Stm3 h Gas pressure in combustion head HR2060 Stm3 h...

Страница 18: ...2270 mm x 1720 mm x 1320 mm L x P x H HR2080 2570 mm x 1900 mm x 1750 mm L x P x H Such packages fear moisture and are not suitable for stacking Packing cases of this type are affected by humidity an...

Страница 19: ...spray adhesive on the flange 5 install the burner into the boiler 6 fix the burner to the stud bolts by means of the fixing nuts according to the picture below 7 After fitting the burner to the boiler...

Страница 20: ...choose the blast tube lenght follow the instructions of the boiler manufacturer In absence of these consider the following Cast iron boilers three pass flue boilers with the first pass in the rear pa...

Страница 21: ...ns ATTENTION Before executing the connections to the gas pipe network be sure that the manual cutoff valves are closed PS PSH PSL PSL PSH PS M M MB DLE VGD MBE gas inlet gas inlet gas inlet Legend 1 F...

Страница 22: ...ording to the procedure set by laws in force CAUTION The direction of gas flow must follow the arrow on the body of the components mounted on the gas ramp valves filters gaskets NOTE the bellows unit...

Страница 23: ...riate sealing agent 2 Insert MB DLE note position of O rings 3 Remove MultiBloc between the threaded flanges 4 After installation perform leakage and functional test 5 Disassembly in reverse order osi...

Страница 24: ...pressure switch 4 PGMAX maximum gas pressure switch 5 Actuator with integrated pressure stabiliser 6 On Off actuator 7 Valve body Threaded 8 Valve body Flange On equipment versions Facile VD R must b...

Страница 25: ...ens VGD VRD SKPx5 Auxiliary optional micro switch Gas valve If the auxiliary microswitch POC is required a dedicated actuator different from the one usually supplied must be ordered The con nection is...

Страница 26: ...the gas train in installed execute the electrical connections for all its items gas valves group gas proving system pressure switches Gas Filter if provided The gas filters remove the dust particles t...

Страница 27: ...o ambient pressure Test atmospheric pressure EV2 clo ses and keep this position for a preset time test time td1 The pressure switch PGCP has not to detect a rise of pressure Test space filling EV1 ope...

Страница 28: ...stallation can be considered self ble please read carefully the warnings chapter at the beginning of this manual 1 3 2 Key 1 Manual valve 2 Light oil filter 3 Light oil feeding pump 4 One way valve 5...

Страница 29: ...ould not contain air pockets Rapid attachment joint should therefore be avoided and threaded or mechanical seal jun ctions preferred Junction threads elbow joints and couplings should be sealed with r...

Страница 30: ...ressure 2 bar Maximum speed 3600 rpm Key 1 Inlet G3 4 2 Pressure gauge port G1 4 3 Vacuum gauge port to measure the inlet vacuum G1 4 4 To pressure adjusting valve G3 4 Key 1 Pressure regulator 2 Pres...

Страница 31: ...trol box please refer to the clabeling recommendations avaible on the Siemens CD attached to the burner WARNING Respect the basic safety rules make sure of the connection to the earthing system do not...

Страница 32: ...NG WITH THESE E G DISCONNECTION EVEN PARTIAL OF THE ELECTRICAL LEADS OPENING THE GENERATOR DOOR DISMANTLING OF PART OF THE BURNER NEVER OPEN OR DISMANTLE ANY COMPONENT OF THE MACHINE EXCEPT FOR ITS MA...

Страница 33: ...lame operation LED B3 Lo flame operation LED B4 Ignition transformer operation LED B5 Fan motor overload tripped LED B6 Stand by signalling lamp G1 Gas valves EV2 operation signalling lamp G2 Gas valv...

Страница 34: ...the actuator goes to the high flame position after some seconds the two stage operation begins the burner is driven automatically to high flame or low flame according to the plant requirements Operati...

Страница 35: ...ust the gas flow rate in the high flame stage as to meet the values requested by the boiler utilisation Start up procedure 1 Turn the burner on 2 the LMV control box starts the system test cycle the A...

Страница 36: ...vides the following items Normal operation by selecting this item and pressing the ENTER key the main page is showed press ESC to go back to the main menu Status Reset it shows system errors or faults...

Страница 37: ...age enter the main menu by pressing the ESC key twice by means of the arrow keys select Params Display press ENTER the system will ask you to enter the proper password by means of the arrow keys selec...

Страница 38: ...the 2 position controller To set these values select the item SD_ModOn SDOn by scrolling down the Load controller menu with the arrow keys and press ENTER the display will show The deafult value for...

Страница 39: ...ime Winter WIN Time operation and the continent EU Europe US United States choose the Summertime Wintertime mode desired and cofirm by pressing ENTER press ESC to exit Set the time zone Time EU US in...

Страница 40: ...This function is already set by the Technical service access by reserved password if this function is enabled when the burner starts upthe Thermal shock protection activated message will be showed If...

Страница 41: ...tand by If the BurnerOn mode is choosen the burner does not follow the modulator and probe settings but operates at the set load For further details see the LMV5x annexed manuals SetLoad Curr 0 0 New...

Страница 42: ...on reduces start flow rate anticlockwise rotation increases it Do not use a screwdriver on the screw VR The pressure stabilizer is adjusted by operating the screw VS located under the cover C By screw...

Страница 43: ...Refit the transparent plastic cover on the pressure switch Calibration the maximum gas pressure switch when provided To calibrate the maximum pressure switch proceed as follows according to its mounti...

Страница 44: ...justment is accomplished Adjustment procedure for light oil operation The light oil flow rate can be adjusted choosing a nozzle that suits the boiler utilisation output and setting the delivery and re...

Страница 45: ...PART III OPERATION 45 Pump flow rate Nozzle flow rate...

Страница 46: ...ig 5 4 As for setting the fuel air ratio curve see the LMV related manual 5 Only if necessary adjust the supply pressure as follows insert a pressure gauge into the port shown on figure and act on on...

Страница 47: ...hole range of the burner output In case of inacceptable values reduce from 20 to 15 the overpressure later on repeat the adjustments described above Pressure governor on return line Pressure governor...

Страница 48: ...e detection electrode photoelement according to the burner models replace it if necessary in case of doubt check the detection circuit after the burner start up Clean and grease leverages and rotating...

Страница 49: ...ed to the last check You can change the filter without removing the fitting 1 Interrupt the gas supply closing the on off valve 2 Remove screws 1 4 using the Allen key n 3 and remove filter cover 5 in...

Страница 50: ...to push 1 2 3 4 5 6 7 1 Position VD on VB fig 2 3 2 Slide VD forward up to the stop fig 4 3 Screw VD on with 2 M5 screws for each max 5 Nm 44 in lb fig 5 6 4 VD can be mounted rotated by 180 fig 7 VB...

Страница 51: ...give the power to any electrical equipmente on the filter Removing the combustion head 1 Remove the top H 2 Remove the UV detector out of its housing disconnect electrode cables and the light oil fle...

Страница 52: ...metallic parts blast tube head etc otherwise the boi ler s operation would be compromised Check the electrodes position after any intervention on the combustion head A B C 696 583 169 747 550 12 75 74...

Страница 53: ...ectrodes position after any intervention on the combustion head ATTENTION avoid the electrode to get in touch with metallic parts blast tube head etc otherwise the boiler operation would be compromise...

Страница 54: ...necessary to carry out a technical diagnosis and if necessary an overall repair The burner status is considered to be at its limit if it is technically impossible to continue using it due to non compl...

Страница 55: ...Check air pressure switch functions and links Burner control damaged Replace burner control BURNER LOCKS OUT WITHOUT ANY GAS FLOW Gas valves don t open Check voltage on valves if necessary replace val...

Страница 56: ...ition transformer or into the electrodes Improve the installation Ignition transformer damaged Replace the transformer PUMP TOO NOISY Suction too high over 0 35 bar dirty filters check valve in the ta...

Страница 57: ......

Страница 58: ......

Страница 59: ......

Страница 60: ...a L Galvani 9 35011 Campodarsego PD ITALY Tel 39 049 9200944 Fax 39 049 9200945 9201269 web site www cibunigas it e mail cibunigas cibunigas it Note specifications and data subject to change Errors an...

Страница 61: ...d an earth external wire for the motor ground The cable for the 4 20mA signal that controls the VSD must be shielded only LMV5x side ends connected to the equipotential terminal If the VSD is not insi...

Страница 62: ...Annex1 Example for motor cable...

Страница 63: ......

Страница 64: ...Annex 2 Example for sensor cable...

Страница 65: ......

Страница 66: ......

Страница 67: ...E Power supply Line voltage Gas L1 High Voltage Transformer N M Power supply Line voltage FE X73 Speed sensor VSD Fan Motor Separate conduit shielded line voltage cable X70 X10 02 X9 01 X4 02 Separate...

Страница 68: ...ion and current fuel throughput The LMV52 system uses an O2 sensor QGO20 an external O2 module and the standard components of the LMV51 sys tem The PLL O2 module is a detached measuring module for the...

Страница 69: ...defined system cables AGG5 641 and AGG5 631 result from the points of intersection in the graph 50 48 46 44 42 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 8 6 4 2 0 0 5 1 25 2 3 5 7 8 AGG5 631 AG...

Страница 70: ......

Страница 71: ...CAN bus cable 100 m Whenever the distance between the LMV5 and the last actuator exceeds 20 m or if more than one SQM48 is used on the burner refer to sizing chart Determination of maximum cable leng...

Страница 72: ...N F T4 AC2 12 V 5 5 3 Not used M L Power trafo 2 AGG5 2 No bus termination No bus termination Bus termination 5 5 5 5 No bus termination No bus termination Installation in the control panel actuator...

Страница 73: ...owered by a sec ond transformer to be located near the actuators and the O2 module Connect the power supply line from that transformer to the O2 module PLL52 in ex ample 3a SA6 in example 3b Auxiliary...

Страница 74: ...n facility 18 8 1 Inputs and outputs Mounting panel shielding connection Communication and power supply for LMV52 Mounting panel shielding connection Communication and power supply Temperature sensor...

Страница 75: ...l o w e d t o j o i n t h e f l u e g a s e s o n t h e i r w a y f r o m t h e b u r n e r t o t h e d e t e c t o r D F l o w v e l o c i t y 1 1 0 m s F l u e g a s t e m p e r a t u r e a t t h e...

Страница 76: ...e p o u r B 1 B 2 B 2 T e n s i o n d e t h e r m o c o u p l e M U 3 S i g n a l d e l l m e n t d e c p m p e n s a t i o n d e t e m p r a t u r e G 2 A l i m e n t a t i o n d e l l m e n t d e c...

Страница 77: ...k s i t i s r e c o m m e n d e d t o l e a v e t h e m e a s u r i n g s y s t e m Q G O a n d R P O s w i t c h e d o n D u r i n g t h e h e a t i n g u p p h a s e t h e d e t e c t o r c o u l d...

Страница 78: ...A G O 2 0 0 0 2 A A R a u c h g a s e i n t r i t t B R a u c h g a s a u s t r i t t C K e r b e D F l a c h d i c h t u n g b e i l i e g e n d L 1 8 0 m m f o r A G O 2 0 0 0 1 A L 2 6 0 m m f o r...

Страница 79: ...r h Transport DIN EN 60 721 3 2 Climatic conditions class 2K2 Mechanical conditions class 2M2 Temperature range 30 70 C Humidity 95 r h Operation DIN EN 60 721 3 3 Climatic conditions class 3K5 Mecha...

Страница 80: ...GND SHIELD 12VAC1 12VAC2 CANH CANL GND SHIELD AZL5 x FE FE SQM4 LMV52 Brown brn White wh Yellow yl Green grn Black blk Brown brn White wh Yellow yl Green grn Black blk Flue gas temperature PLL52 PLL5...

Отзывы: