UltraGlow G33R-1 Zero Clearance Rear Vent Direct Vent Gas Fireplace

6

Diagram 1

INSTALLATION

LOCATING YOUR 

GAS STOVE

1)

  When selecting a location for your stove, 

ensure that the clearances outlined on this 
page are met.

2)

  Provide adequate clearances for servic-

ing.

3)

  The appliance must be installed on a fl at, 

solid, continuous surface (e.g. wood, metal, 
concrete). This may be the fl oor, or raised up 
on a platform to enhance its visual impact. 
If the appliance is going to be installed 
on carpeting, combustible linoleum tile or 
other combustible material other than wood 
fl ooring, the appliance must be installed on 
a metal or wood panel extending the full 
width and depth of the appliance.

4)

  The G33R-1 Direct Vent Gas Fireplace 

can be installed in a recessed position or 
framed out into the room as in A, B, C, D. 
See Diagram 1.

5)

  This appliance is Listed for bedroom  instal-

lations when used with a Listed Millivolt 
Thermostat. Some areas may have further 
requirements, check local codes before 
installation.

6)

  The G33R-1 Direct Vent Gas Fireplace is 

approved for alcove installations, which 
meet the clearances listed on this page.

7) 

We recommend that you plan your instal-
lation on paper using exact measurements 
for clearances and fl oor protection before 
actually installing this appliance. Have a 
qualifi ed inspector, dealer, or installer review 
your plans before installation.

Clearances Flush Front

UNIT DIMENSIONS

MANUFACTURED 

MOBILE HOME

ADDITIONAL 

REQUIREMENTS

1)

  Ensure that structural members are not cut 

or weakened during installation.

2)

  Ensure proper grounding using the #8 ground 

lug provided. See page 26.

A)

  Flat on Wall

B)

  Flat on Wall Corner

C)

  Recessed into Wall/Alcove

D)

 Corner 

 

Note:   For vent terminations see page 9.

CLEARANCES

The clearances listed below are Minimum 
distances unless otherwise stated:

A major cause of chimney related 
fi res is failure to maintain required 
clearances (air space) to combus-
tible materials. It is of the greatest 
importance that this fi replace and 
vent system be installed only in ac-
cordance with these instructions.

Clearance to Combustibles from:

 Back

 0" 

(0mm) 

 Side

 0" 

(0mm) 

 

 

Floor

 0" 

(0mm) 

 

NOTE: The minimum fl oor clearance must be 
maintained from the top surface of the carpet-
ing, tile, etc.

   

Minimum Clearance from Top of Unit to:
 Mantel* 

min. 7"  (177mm) 

 Ceiling

 30" 

(762mm)

   

from top of unit.

* see mantle clearance instructions (page 7).

Side Wall Clearance 
  Bay or Flush Front

 7-1/2"  (191mm)

Vent
 

Flex 1-1/2" 

(38mm)

 Simpson 

Dura-Vent 1-1/4"  (32mm)

 

Alcove Clearances:

 Max. 

Depth

 36" 

(914mm)

 Min. 

Width

 48" 

(1219mm)

 Min. 

Height

 59" 

(1499mm)

WARNING

Fire hazard is an extreme risk 

if these clearances are 

not adhered to.

The 

HeatWave

 Duct Kit has different clear-

ance and framing requirements, check the 

HeatWave

 manual for details.

Содержание UltraGlow G33R-NG1 Natural Gas

Страница 1: ...y appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot re...

Страница 2: ...bears our own mark it promises to provide you with economy comfort and security for many trouble free years to follow Please take a moment now to acquaint yourself with these instructions and the man...

Страница 3: ...nts 6 Unit Dimensions 6 Clearances 6 Combustible Mantel Clearances 7 Mantel Leg Clearance 7 Framing and Finishing 8 Exterior Vent Termination Locations 9 Unit Assembly Prior to Installation 10 Venting...

Страница 4: ...lass option MUST APPAREIL FONCTIONNANT AU NATURAL GAS CONCU POUR ETRE POELE Mod le G33R NG Pression d allimentation minimum Pression a la tubulure d chappement lev e Pression a la tubulure d chappemen...

Страница 5: ...our gas appliances checked annually 13 Do not slam shut or strike the glass door 14 Under no circumstances should any solid fuels wood paper cardboard coal etc be used in this appliance 15 The applian...

Страница 6: ...nstalling this appliance Have a quali edinspector dealer orinstallerreview your plans before installation Clearances Flush Front UNIT DIMENSIONS MANUFACTURED MOBILE HOME ADDITIONAL REQUIREMENTS 1 Ensu...

Страница 7: ...ible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board This drawing is to scale at 1 6 one inch 6 inches Mantel can be installed anyw...

Страница 8: ...nit does not have to be com pletely enclosed in a chase The clearance on top of the unit is 0 to thestandoffssocombustiblebuilding materials can be laid directly on top of the standoffs You must maint...

Страница 9: ...er Not to be installed above a meter regulator assembly within 3 90cm horizontally from the centerline of the regulator Clearance to service regulator vent outlet Min 36 90cm Clearance to non mechanic...

Страница 10: ...t not be con nected to any other appliance The gas appliance and vent system must be vented directly to the outside of the building and never be attached to a chimney serving a separate solid fuel or...

Страница 11: ...t be used to ensure that the termination is not recessed into the siding 2 Level the replace and fasten it to the fram ing using nails or screws through the nailing strips 3 Assemble the vent assembly...

Страница 12: ...945BG N A N A 90O Elbow Galvinized 990 4DT EL90S 4D90LS 90O Elbow Black 990B 4DT EL90SB 4D90LBS 90O Elbow Swivel Galvinized 990G N A N A 90O Elbow Swivel Black 990BG N A N A Ceiling Support 949 n a fr...

Страница 13: ...for installations with a maximum continuous vent length of 10 ft 3 0m Note Must use optional rigid pipe adaptor Part 510 994 when using Rigid Pipe vent systems Maintain a 1 1 4 clearance to combustib...

Страница 14: ...ce to combustibles Note Must use optional rigid pipe adaptor when using rigid pipe vent systems Part 510 994 RIGID PIPE VENTING ARRANGEMENTS VERTICAL TERMINATIONS Propane Natural Gas The shaded area i...

Страница 15: ...Flue Adaptor in conjunction with Selkirk Direct Temp and Ameri Vent Direct venting systems Use of these systems with the Direct Vent GS starting collar is deemed accept able and does not affect the I...

Страница 16: ...r Intake pipe must be attached to the inlet air collar of the termination cap Required Parts Part Description 946 529 Co linear DV Vertical Termination Cap 948 305 3 Flex 35 ft 946 563 Co Axial to Co...

Страница 17: ...ect Vent Gas Fireplace 17 Venting Arrangements Vertical Terminations with Co linear Flex System for both Residential Manufactured Homes into Masonry Fireplaces The shaded area in the diagrams show the...

Страница 18: ...uare hole should line up with the centerline of the horizontal pipe Cut and frame the 10 inch square hole in the exterior wall where the vent will be terminated If the wall being penetrated is constru...

Страница 19: ...lar over the pipe section and seal with a mastic 8 Install the vertical termination cap by twist locking it Note Anyclosetsorstoragespaces which the vent passes through must be enclosed Diagram 1 Diag...

Страница 20: ...ected for servicing Flare nuts for copper lines and ex connectors are usually considered to meet this requirement Important Alwayscheckforgasleakswitha soapandwatersolutionorgasleakdetector Do not use...

Страница 21: ...r OUT pressure tap s using a 5 16 ID hose INSTALLATION PILOT ADJUSTMENT Periodically check the pilot ames Correct ame pattern has three strong blue ames 1 owing around the thermopile 1 around the ther...

Страница 22: ...Notch Bracket Bracket 254 250 254 5 Position Log 253 across the cutouts in Logs 250 and 254 with the notch on the left side of the log tting into the 2nd grate tab Cutouts 2nd Grate Tab 253 250 254 5t...

Страница 23: ...Optional If you require extra space to slide the fan to the back the left spring can be unhooked from the bracket Note A 120 Volt AC power cord can be in stalled at rough in stage so that the poweris...

Страница 24: ...spring See diagram 3 To remove the ush door reverse the above steps INSTALLATION Diagram 1 FLUSH DOOR The standard ush door comes with a black frame To install the frame simply hook the top door ange...

Страница 25: ...convenient location on the wall to install the receiver and the receptacle box protection from extreme heat is very important Run wires from the replace to that location Use Thermostat Wire Table 2 Co...

Страница 26: ...ck is provided on the left hand side of the unit A three wire power cord can also be used and plugged into a suitable receptacle Do not cut the ground terminal off under any circumstances NOTE Even if...

Страница 27: ...The unit should never be turned off and on again without a minimum of a 60 second wait 2 Turn gas control knob so indicator points to OFF position and allow 5 minutes for any gas in the combustion cha...

Страница 28: ...anauthorizedRegency Installer at the time of installation or service AERATION ADJUSTMENT The air shutter can be adjusted by moving the adjustingwireupordown Thewireisaccessed through the bottom louver...

Страница 29: ...ss gasket for the Bay Front Part 936 243 and a tadpole glass gasket for the Flush Front Part 936 155 MAINTENANCE INSTRUCTIONS 1 Alwaysturnoffthegasvalvebeforecleaning For relighting refer to lighting...

Страница 30: ...the louvers 18 Fire up the unit again and check for proper ame appearance and glow on logs Diagram 2 Rear Log Stand and Valve Tray Assembly screws Valve Tray Assembly Rear Log Stand screws REMOVING VA...

Страница 31: ...de Back 27 Outer Flue Collar 28 Inner Flue Collar Assembly 30 Gasket Flue Collar 31 Flue Mounting Plate 331 917 Complete Fan Assembly Optional 34 910 331 P Fan Moter 120 V 330 520 Flush Door Assembly...

Страница 32: ...l Gas 910 380 S I T Valve Propane 58 Valve Bracket 59 Firebox Base 65 Pilot Bracket 66 910 034 Pilot Assy 3 way ame Convertible Top S I T Natural Gas 910 035 Pilot Assy 3 way ame Convertible Top S I T...

Страница 33: ...____________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ _______________...

Страница 34: ...__________________________________________________ ___________________________________________________ ___________________________________________________ _____________________________________________...

Страница 35: ...urchase date serial type of unit problem and part or parts requested without this information the warranty will be invalid Exclusions This Warranty does not extend to or include paint door or glass ga...

Страница 36: ..._________________________________________________ Phone ___________________________________________________________ Date Installed ______________________________________________________ Serial No ____...

Отзывы: