UltraGlow G33R-1 Zero Clearance Rear Vent Direct Vent Gas Fireplace

18

HORIZONTAL 

INSTALLATIONS

Install the vent system according to the 
manufacturer's instructions included with the 
components.

1)

  Set the unit in its desired location. Check 

to determine if wall studs or roof rafters 
are in the way when the venting system is 
attached. If this is the case, you may want 
to adjust the location of the unit. Rough in 
the gas preferably on the right side of the 
unit and the electrical (junction block is on 
the left side) on the left.

2)

  Direct Vent pipe and fi ttings are designed 

with special twist-lock connections to con-
nect the venting system to the appliance 
fl ue outlet. A twist-lock appliance adaptor 
is an available option that must be used in 
conjunction with the Simpson Dura-Vent 
Direct Vent GS system. 

3)

  Put a bead of silicone inside the outer 

section of the adapter and a bead of Stove 
Mate on the inner collar. Slip the adapter 
over the existing inner and outer fl ue collar 
and fasten to the outer collar only with the 
3 supplied screws (drilling pilot holes will 
make this easier). Level the fi replace and 
fasten it to the framing using nails or screws 
through the nailing strips.

4)

  Assemble the desired combination of pipe 

and elbows to the appliance adaptor and 
twist-lock for a solid connection.

Note:

 

a) 

  Twist-lock procedure: Four indentations, 

located on  the female ends of pipes and 
fi ttings, are designed to  slide straight 
onto the male ends of adjacent pipes 
and fi ttings, by orienting the four pipe 
indentations so they match and slide 
in to the four entry slots on the male 
ends, Diagram 1. Push the pipe sections 
completely  together, then twist-lock 
one section clockwise approximately 
one-quarter turn, until the two sections 
are fully locked. The female locking lugs 
will not be visible from the outside, on 
the Black Pipe or fi ttings. They may be 
located by examining the inside of the 
female ends.   

Note:   Apply sealant "Mill-Pac" to inner pipe 

Diagram 1

and high temperature silicone seal-
ant to outer pipe on every twist-lock 
joint.

Diagram 3

 b)

  Horizontal runs of vent must be sup-

ported every three feet. Wall straps are 
available for this  purpose.

5)

  Mark the wall for a 10" x 10"  square hole. 

The center of the square hole should line 
up with the centerline of the horizontal pipe. 
Cut and frame the 10 inch square hole in 
the exterior wall where the vent will be 
terminated. If the wall being penetrated is 
constructed of non-combustible material, 
i.e. masonry block or concrete, a 7"(178mm) 
diameter (7-1/2"(191mm) dia. for fl ex) hole 
is acceptable. See Horizontal Termination 
diagram on page 13.

Note:  With Dura-Vent, the minimum height 

is achieved by installing a 90

o

 elbow 

directly to the rigid pipe adaptor.

Note:
 a)

  The horizontal run of vent must be level, 

or have a 

 

 

1/4 inch rise for every 1 foot of run to-
wards the termination. Never allow the 
vent to run downward. This could cause 
high temperatures and may present the 
possibility of a fi re.

 

b)

  The location of the horizontal vent termi-

nation on an exterior wall must meet all 
local and national building codes, and 
must not be blocked or obstructed.  For 
External Vent Terminal Locations, see 
diagram on page 9.

 

c)

 

Snorkel Terminations:

 

 

For installations requiring a vertical rise 
on the exterior of the building, 14-inch 
and 36-inch tall Snorkel Terminations 
and the Riser Vent  as shown in Dia-
gram 2 & 2a are available. Follow the 
same installation procedures as used 
for standard Horizontal Termination. 
NEVER install the snorkel upside 
down.

*As specifi ed in CGA B149 Installation Code. 
Local codes or regulations may require different 
clearances.

Diagram 2

 

Below Grade Snorkel Installation

 

If the Snorkel Termination must be installed 
below grade, i.e. basement application, 
proper drainage must be provided to prevent 
water from entering the Snorkel Termination. 
Refer to Dura-Vent Installation instructions 
for details. Do not attempt to enclose the 
Snorkel within the wall, or any other type 
of enclosure.

6)

 

The arrow on the vent cap should be 
pointing up.

 Insure that the 1-1/2" clear-

ances to combustible materials are main-
tained (Diagram 3). Install the termination 
cap.

Diagram 2a

 

The four wood screws provided should 
be replaced with appropriate fasteners for 
stucco, brick, concrete, or other types of 
sidings.

Note:  If installing termination on a siding 

covered wall, a vinyl siding standoff 
or furring strips must be used to 
ensure that the termination is not 
recessed into the siding.

 

7)

  Before connecting the horizontal run of vent 

pipe to the vent termination, slide the Wall 
Thimble (Part # 620-926) over the vent 
pipe.

8)

  Slide the appliance and vent assembly 

towards the wall carefully inserting the 

INSTALLATION

Содержание UltraGlow G33R-NG1 Natural Gas

Страница 1: ...y appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot re...

Страница 2: ...bears our own mark it promises to provide you with economy comfort and security for many trouble free years to follow Please take a moment now to acquaint yourself with these instructions and the man...

Страница 3: ...nts 6 Unit Dimensions 6 Clearances 6 Combustible Mantel Clearances 7 Mantel Leg Clearance 7 Framing and Finishing 8 Exterior Vent Termination Locations 9 Unit Assembly Prior to Installation 10 Venting...

Страница 4: ...lass option MUST APPAREIL FONCTIONNANT AU NATURAL GAS CONCU POUR ETRE POELE Mod le G33R NG Pression d allimentation minimum Pression a la tubulure d chappement lev e Pression a la tubulure d chappemen...

Страница 5: ...our gas appliances checked annually 13 Do not slam shut or strike the glass door 14 Under no circumstances should any solid fuels wood paper cardboard coal etc be used in this appliance 15 The applian...

Страница 6: ...nstalling this appliance Have a quali edinspector dealer orinstallerreview your plans before installation Clearances Flush Front UNIT DIMENSIONS MANUFACTURED MOBILE HOME ADDITIONAL REQUIREMENTS 1 Ensu...

Страница 7: ...ible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board This drawing is to scale at 1 6 one inch 6 inches Mantel can be installed anyw...

Страница 8: ...nit does not have to be com pletely enclosed in a chase The clearance on top of the unit is 0 to thestandoffssocombustiblebuilding materials can be laid directly on top of the standoffs You must maint...

Страница 9: ...er Not to be installed above a meter regulator assembly within 3 90cm horizontally from the centerline of the regulator Clearance to service regulator vent outlet Min 36 90cm Clearance to non mechanic...

Страница 10: ...t not be con nected to any other appliance The gas appliance and vent system must be vented directly to the outside of the building and never be attached to a chimney serving a separate solid fuel or...

Страница 11: ...t be used to ensure that the termination is not recessed into the siding 2 Level the replace and fasten it to the fram ing using nails or screws through the nailing strips 3 Assemble the vent assembly...

Страница 12: ...945BG N A N A 90O Elbow Galvinized 990 4DT EL90S 4D90LS 90O Elbow Black 990B 4DT EL90SB 4D90LBS 90O Elbow Swivel Galvinized 990G N A N A 90O Elbow Swivel Black 990BG N A N A Ceiling Support 949 n a fr...

Страница 13: ...for installations with a maximum continuous vent length of 10 ft 3 0m Note Must use optional rigid pipe adaptor Part 510 994 when using Rigid Pipe vent systems Maintain a 1 1 4 clearance to combustib...

Страница 14: ...ce to combustibles Note Must use optional rigid pipe adaptor when using rigid pipe vent systems Part 510 994 RIGID PIPE VENTING ARRANGEMENTS VERTICAL TERMINATIONS Propane Natural Gas The shaded area i...

Страница 15: ...Flue Adaptor in conjunction with Selkirk Direct Temp and Ameri Vent Direct venting systems Use of these systems with the Direct Vent GS starting collar is deemed accept able and does not affect the I...

Страница 16: ...r Intake pipe must be attached to the inlet air collar of the termination cap Required Parts Part Description 946 529 Co linear DV Vertical Termination Cap 948 305 3 Flex 35 ft 946 563 Co Axial to Co...

Страница 17: ...ect Vent Gas Fireplace 17 Venting Arrangements Vertical Terminations with Co linear Flex System for both Residential Manufactured Homes into Masonry Fireplaces The shaded area in the diagrams show the...

Страница 18: ...uare hole should line up with the centerline of the horizontal pipe Cut and frame the 10 inch square hole in the exterior wall where the vent will be terminated If the wall being penetrated is constru...

Страница 19: ...lar over the pipe section and seal with a mastic 8 Install the vertical termination cap by twist locking it Note Anyclosetsorstoragespaces which the vent passes through must be enclosed Diagram 1 Diag...

Страница 20: ...ected for servicing Flare nuts for copper lines and ex connectors are usually considered to meet this requirement Important Alwayscheckforgasleakswitha soapandwatersolutionorgasleakdetector Do not use...

Страница 21: ...r OUT pressure tap s using a 5 16 ID hose INSTALLATION PILOT ADJUSTMENT Periodically check the pilot ames Correct ame pattern has three strong blue ames 1 owing around the thermopile 1 around the ther...

Страница 22: ...Notch Bracket Bracket 254 250 254 5 Position Log 253 across the cutouts in Logs 250 and 254 with the notch on the left side of the log tting into the 2nd grate tab Cutouts 2nd Grate Tab 253 250 254 5t...

Страница 23: ...Optional If you require extra space to slide the fan to the back the left spring can be unhooked from the bracket Note A 120 Volt AC power cord can be in stalled at rough in stage so that the poweris...

Страница 24: ...spring See diagram 3 To remove the ush door reverse the above steps INSTALLATION Diagram 1 FLUSH DOOR The standard ush door comes with a black frame To install the frame simply hook the top door ange...

Страница 25: ...convenient location on the wall to install the receiver and the receptacle box protection from extreme heat is very important Run wires from the replace to that location Use Thermostat Wire Table 2 Co...

Страница 26: ...ck is provided on the left hand side of the unit A three wire power cord can also be used and plugged into a suitable receptacle Do not cut the ground terminal off under any circumstances NOTE Even if...

Страница 27: ...The unit should never be turned off and on again without a minimum of a 60 second wait 2 Turn gas control knob so indicator points to OFF position and allow 5 minutes for any gas in the combustion cha...

Страница 28: ...anauthorizedRegency Installer at the time of installation or service AERATION ADJUSTMENT The air shutter can be adjusted by moving the adjustingwireupordown Thewireisaccessed through the bottom louver...

Страница 29: ...ss gasket for the Bay Front Part 936 243 and a tadpole glass gasket for the Flush Front Part 936 155 MAINTENANCE INSTRUCTIONS 1 Alwaysturnoffthegasvalvebeforecleaning For relighting refer to lighting...

Страница 30: ...the louvers 18 Fire up the unit again and check for proper ame appearance and glow on logs Diagram 2 Rear Log Stand and Valve Tray Assembly screws Valve Tray Assembly Rear Log Stand screws REMOVING VA...

Страница 31: ...de Back 27 Outer Flue Collar 28 Inner Flue Collar Assembly 30 Gasket Flue Collar 31 Flue Mounting Plate 331 917 Complete Fan Assembly Optional 34 910 331 P Fan Moter 120 V 330 520 Flush Door Assembly...

Страница 32: ...l Gas 910 380 S I T Valve Propane 58 Valve Bracket 59 Firebox Base 65 Pilot Bracket 66 910 034 Pilot Assy 3 way ame Convertible Top S I T Natural Gas 910 035 Pilot Assy 3 way ame Convertible Top S I T...

Страница 33: ...____________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ _______________...

Страница 34: ...__________________________________________________ ___________________________________________________ ___________________________________________________ _____________________________________________...

Страница 35: ...urchase date serial type of unit problem and part or parts requested without this information the warranty will be invalid Exclusions This Warranty does not extend to or include paint door or glass ga...

Страница 36: ..._________________________________________________ Phone ___________________________________________________________ Date Installed ______________________________________________________ Serial No ____...

Отзывы: