Single phase operation
Connect the power source under test to CAM-LOK connectors provided on the load bank
using suitable mating CAM-LOK plugs and cables sized per the NEC (National Electric
Code) or any local codes.
The Load Bank is provided with color coded qty.01 CAM-LOK connectors (400A Max.) for
each phase (L1/L2/L3) and One Connector for Ground Cable connection.
Connect CAM-LOK plugs to the Phase (L1) Black, Phase (L3) Blue and put jumper
between Phases (Red L2-Blue L3) as shown below Image. (see figure-8)
Connect external 120VAC, 1-Phase, 50/60Hz, 10A Power Source using supplied cord with
plug to the load bank.
Figure-8 Single Phase connection
HMI Display (E1A) on hand held unit will turn on.
Use main screen on HMI display (as shown below figure-9) to set require KW.