Operation
Connect the power source under test to CAM-LOK connectors provided on the load bank
using suitable mating CAM-LOK plugs and cables sized per the NEC (National Electric
Code) or any local codes.
The Load Bank is provided with color coded qty.01 CAM-LOK connectors (400A Max.) for
each phase (L1/L2/L3) and One Connector for Ground Cable connection.
Load cable conductors from the power source to the load bank and mating CAM-LOK
cable plugs should be adequately sized and protected to handle the maximum rated load
and in accordance to the
National Electric Code and any local codes
.
Turn on the power source under test.
Connect external 120VAC,1-Phase, 50/60Hz, 10A Power Source using supplied
cord with plug to the load bank.
HMI Display (E1A) on hand held unit will turn on.
Use main screen on HMI display (as shown below figure-1) to set require KW.
Figure-1 Main Screen.