IM_ONE_Safety-07
www.ueonline.com
1
GENERAL
MISUSE OF THIS PRODUCT MAY CAUSE EXPLOSION AND PERSONAL INJURY. THESE INSTRUCTIONS MUST BE THOROUGHLY READ AND UNDERSTOOD
BEFORE UNIT IS INSTALLED. SEE THE PRODUCT NAMEPLATE INFORMATION FOR SPECIFIC AGENCY CERTIFICATIONS APPLICABLE TO YOUR PRODUCT.
SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR USE IN HAZARDOUS LOCATIONS.
FOR ZONE HAZARDOUS LOCATIONS, ALL CABLE ENTRY DEVICES SHALL BE CERTIFIED IN TYPE OF EXPLOSION PROTECTION FLAMEPROOF ENCLOSURE “d”
WITH AN IP66 RATING, SUITABLE FOR THE CONDITIONS OF USE AND CORRECTLY INSTALLED. IF CABLES AND CABLE GLANDS ARE NOT USED, A STOPPING
BOX SHALL BE PROVIDED WITHIN 2” (5CM) OF THE ENCLOSURE. FLAMEPROOF JOINT AND GAP DETAILS ARE PROVIDED ON PAGE 2.
INSTALL UNITS WHERE SHOCK, VIBRATION AND TEMPERATURE FLUCTUATIONS ARE MINIMAL. ORIENT UNIT TO PREVENT MOISTURE FROM ENTERING
ENCLOSURE. USE PROPERLY RATED SEALING FITTINGS FOR ELECTRICAL WIRE ENTRY. DO NOT MOUNT UNIT IN AMBIENT TEMPERATURES EXCEEDING
PUBLISHED LIMITS. THIS IS ESPECIALLY CRITICAL FOR LOCAL MOUNT TEMPERATURE UNITS. USE OF A SHROUD IS RECOMMENDED WHERE DIRECT SUNLIGHT
AND RAIN MAY COME IN CONTACT WITH THE ENCLOSURE.
IN ORDER TO MEET THE ELECTROMAGNETIC COMPATIBILITY REQUIREMENTS SPECIFIED IN EN61000-6-2: IMMUNITY FOR INDUSTRIAL ENVIRONMENTS,
EXTERNAL WIRING MUST BE RUN USING CABLE WITH A GROUNDED SHIELD OR CABLE RUN INSIDE OF A GROUNDED METAL CONDUIT
INTERFERENCE FROM IMPROPERLY SHIELDED VFD’S (VARIABLE FREQUENCY DRIVES) AND MOTOR CONTROLLERS MAY CAUSE NUISANCE TRIPS.
DURING INSTALLATION, MARK THE BOX NEXT TO EACH PROTECTION METHOD ON THE NAMEPLATE THAT APPLIES TO YOUR APPLICATION.
THIS EQUIPMENT IS CERTIFIED IN ACCORDANCE WITH THE REQUIREMENTS OF THE FOLLOWING APPLICABLE STANDARDS (SEE TABLE 1) AND
IS SUITABLE FOR USE IN NON-HAZARDOUS AND THE FOLLOWING HAZARDOUS LOCATIONS, AND IS ATEX AND IECEX CERTIFIED SUITABLE FOR
APPROPRIATE USE IN GAS AND DUST ZONE 1 APPLICATIONS.
Model 2SLP
N. America
Europe
International
Flameproof
Cert Number:
UL File E226592
DEMKO 09 ATEX 0813748X
IECEx UL 08.0017X
Applicable
Standards
UL 50, UL 50E, UL 61010-1, UL 1203, CSA C22.2 No.
25-1966, CSA C22.2 No. 30-M1986, CSA C22.2 No.
94.01-07, CSA C22.2 No. 94.02-07, CSA C22.2 No.
61010-1, UL 60079-0, UL 60079-1, CSA 22.2 No.
60079-0:11, CSA 22.2 No. 60079-1:11
EN 60079-0: 2012 + A11:2013
EN 60079-1:2014
EN 60079-31:2014
IEC 60079-0, Ed.6 (2011-06)
+ Corr.1 (2012-01) + Corr.2
(2013-12)
IEC 60079-1:Ed.7
IEC 60079-31:Ed.2
Suitable for
appropriate use in:
Class I, Div. 1, Groups A, B, C & D
Class II, Div. 1 Groups E, F & G
Class III
Class I, Zone 1 AEx db IIC T3/T5*
Ex d IIC T3/T5*
II 2 G Ex db IIC T3/T5* Gb
II 2 D Ex tb IIIC T90°C Db
IP66
-40°C ≤ TAMB ≤ +70°C
Ex db IIC T3/T5* Gb
Ex tb IIIC T90°C Db
IP66
-40°C ≤ TAMB ≤ +70°C
*Straight pressure sensor models P06-P16 have a temperature class of T3, all others T5
FLAMEPROOF AND DUST-IGNITION PROOF - SPECIAL CONDITIONS FOR SAFE USE
• Field wiring must be rated 105°C minimum. For ambient temperatures below -10°C, use suitable field wiring.
• Blanking elements from factory have been tested for flameproof “d” and dust “tb” with the enclosure as an assembly and carry no markings.
• A suitable thermowell made from corrosion-resistant material and engaging 5 threads minimum (with thread sealant) is required for the local
spring loaded temperature sensor to maintain IP66
One Series
Field Safety System™
Electronic Pressure, Differential Pressure,
and Temperature Transmitter Switch
Model: 2SLP
U N I T E D E L E C T R I C
C O N T R O L S
Installation and Maintenance
Instructions
IM_ONE_Safety-07
Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of Recommended
Practices, Liabilities and Warranties. All Warnings are translated to French and can be found of pages 22 and 23.
Table 1