63
105294-05 - 5/15
Figure 7.47
:
Condensate Piping arrangement
VII. Venting
I. Condensate Trap and Drain Line (continued)
Warning
Asphyxiation Hazard. Failure to install the condensate drain in accordance with the above instructions
could cause flue gas to enter the building, resulting in personal injury or death.
nOTiCE
Boiler condensate is corrosive. Route condensate drain line in a manner such that any condensate
leakage will not cause property damage.
Some jurisdictions may require that condensate be neutralized prior to disposal.
Use materials approved by the authority having jurisdiction.
I. Condensate Trap and Drain Line
All condensate which forms in the boiler or vent system passes through the heat exchanger and out of a bottom drain
port which is connected to the condensate trap with a hose. This trap allows condensate to drain from the heat exchanger while
retaining flue gases in the boiler. This trap is an integral part of the boiler but must be connected to a drain pipe as shown in
Figure 7.47
.
A length of corrugated tubing is supplied with the boiler and is connected to the trap as shown in Figure 747. Note
the following when disposing of the condensate:
1. If the corrugated condensate drain line must be extended, construct the extension from PVC or CPVC pipe.
Insert the hose
provided with the boiler into the end of the extension as shown in Figure 7.47.
2. Condensate is slightly acidic. Do not use metallic pipe or fittings in the condensate drain line. Do not route the drain line
through areas that could be damaged by leaking condensate.
3. Some jurisdictions may require that the condensate be neutralized before being disposed of. Dispose of condensate in
accordance with local codes.
4. Do not route, or terminate, the condensate drain line in areas subjected to freezing temperatures.
5. If the point of condensate disposal is above the trap, it will be necessary to use a condensate pump to move the condensate
to the drain. In such cases, select a condensate pump that is approved for use with condensing boilers. If overflow from this
pump would result in property damage, select a pump with an overflow switch and use this switch to shut down the boiler.
Alternatively, if heat is a necessity, use the overflow switch to trigger an alarm.
6. Do not attempt to move the trap from the location shown in Figure 7.47. Do not attempt to substitute another trap for the one
provided with the boiler.
7. The vent shown in Figure 7.47 must be left open for the trap to work properly.
Содержание K2
Страница 10: ...10 105294 05 5 15 Figure 4 1 Minimum Clearances To Combustible Construction IV Locating the Boiler continued ...
Страница 12: ...12 105294 05 5 15 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Страница 37: ...37 105294 05 5 15 THIS PAGE LEFT BLANK INTENTIONALLY ...
Страница 69: ...69 105294 05 5 15 Figure 9 2 Piping Method 1 Near Boiler Piping Heating Only IX System Piping continued ...
Страница 74: ...74 105294 05 5 15 Figure 9 6 Piping Method 1 Near Boiler Piping Shaded Boiler Loop IX System Piping continued ...
Страница 84: ...84 105294 05 5 15 Figure 10 4 Proper Installation of Header Sensor X Wiring continued ...
Страница 86: ...86 105294 05 5 15 X Wiring continued ...
Страница 87: ...87 105294 05 5 15 Figure 10 6 Internal Wiring Connections Diagram X Wiring continued ...
Страница 89: ...89 105294 05 5 15 Figure 10 8 TACO SR504 or Equivalent Zone Panel Wiring Connection Diagram X Wiring continued ...
Страница 90: ...90 105294 05 5 15 X Wiring continued Figure 10 9 Sage Zone Control Circulator Panel Wiring Connection Diagram ...
Страница 97: ...97 105294 05 5 15 Lighting and Operating Instructions XI Start Up and Checkout continued ...
Страница 106: ...106 105294 05 5 15 ...
Страница 107: ...107 105294 05 5 15 ...
Страница 108: ...108 105294 05 5 15 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...