91
105294-05 - 5/15
Use the following procedure for initial start-up of the boiler:
1) Verify
that the venting, water piping, gas piping and electrical system are installed properly.
2)
Confirm all electrical, water and gas supplies are turned off at the source and that vent is clear of obstructions.
3)
Confirm that all manual shut-off gas valves between the boiler and gas source are closed.
4)
If not already done, flush the system to remove sediment, flux, and traces of boiler additives.
5) Fill the boiler and hydronic system with water meeting the following requirements below (also see the note on the next
page):
•
pH between 6.5 and 9.5
•
Hardness less than 7 grains/gallon
•
Chlorides less than 200 ppm
•
Pressurize the system to at least 12 psi at the boiler
6) Bleed air from the heat exchanger using the manual air vent in the top left side of the heat exchanger (Figure 11.1). To do
this install a piece of ¼” ID clear tubing over the hose barb and route the tubing to a location where water will not dam-
age controls or nearby construction. Turn vent counter clockwise and allow heat exchanger to vent until a steady stream
of water is observed. Close vent and remove hose.
7)
Check all gas piping for leaks and purge piping sections that are filled with air. Refer to the
National Fuel Gas Code
for
additional information on testing and purging gas lines.
8)
Confirm vent system is complete and free of obstructions before attempting to fire boiler.
9) Inspect all wiring for loose, uninsulated or miswired connections.
10) If the boiler is to be converted to propane, convert as described in Appendix A. If boiler is operating at elevations above
2000ft, see Appendix B of this manual for setup instructions.
XI. Start-Up and Checkout
Warning
Burn Hazard. The maximum operating pressure of this boiler is 30 psig (210 kPa) or 50 psig (340 kPa),
depending on the model and safety relief valve option selected. Never exceed the maximum allowable
working pressure on the heat exchanger aSME plate.
DangEr
Explosion Hazard. Do not use matches, candles, open flames or other ignition source to check for
leaks.
Make sure that the area around the boiler is clear and free from combustible materials, gasoline and
other flammable vapors and liquids.
Warning
Completely read, understand and follow all instructions in this manual before attempting start-up.
nOTiCE
Safe lighting and other performance criteria were met with the gas train assembly provided on the boiler
when the boiler underwent the test specified in Z21.13.
Содержание K2
Страница 10: ...10 105294 05 5 15 Figure 4 1 Minimum Clearances To Combustible Construction IV Locating the Boiler continued ...
Страница 12: ...12 105294 05 5 15 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Страница 37: ...37 105294 05 5 15 THIS PAGE LEFT BLANK INTENTIONALLY ...
Страница 69: ...69 105294 05 5 15 Figure 9 2 Piping Method 1 Near Boiler Piping Heating Only IX System Piping continued ...
Страница 74: ...74 105294 05 5 15 Figure 9 6 Piping Method 1 Near Boiler Piping Shaded Boiler Loop IX System Piping continued ...
Страница 84: ...84 105294 05 5 15 Figure 10 4 Proper Installation of Header Sensor X Wiring continued ...
Страница 86: ...86 105294 05 5 15 X Wiring continued ...
Страница 87: ...87 105294 05 5 15 Figure 10 6 Internal Wiring Connections Diagram X Wiring continued ...
Страница 89: ...89 105294 05 5 15 Figure 10 8 TACO SR504 or Equivalent Zone Panel Wiring Connection Diagram X Wiring continued ...
Страница 90: ...90 105294 05 5 15 X Wiring continued Figure 10 9 Sage Zone Control Circulator Panel Wiring Connection Diagram ...
Страница 97: ...97 105294 05 5 15 Lighting and Operating Instructions XI Start Up and Checkout continued ...
Страница 106: ...106 105294 05 5 15 ...
Страница 107: ...107 105294 05 5 15 ...
Страница 108: ...108 105294 05 5 15 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...